BOP HIPWR 111315
2-21
2.8.4
CONFIGURING PARALLEL, SERIES, 2 X 2 OR 3 X 2 COMBINATIONS
1. To configure a unit to be designated as a slave proceed as follows:
a. Turn on power only to the unit to be designated as a slave.
b. From the power-up screen press
%
to enter the General Setup Menu. Highlight Series/
Parallel and press
!
to view the Multiple Units menu (see Table 2-12). If required, enter
password (see PAR. 3.2.4.3) before continuing.
c. From the Multiple Units menu, highlight
Configuration
(use
ADJUST
control or the
Y
or
U
keys) and press
!
to modify. When prompted, enter ADMIN2 password (see PAR.
3.2.4.3). Select
Series
,
Parallel
,
Master 2X2
or
Master 3X2
and press
$
to apply
the change.
d. If either
Series
or
Parallel
were selected in step d above,
Connection Type
shows
Series
or
Parallel
as selected. Highlight
Unit Type
and press
!
to modify. High-
light
SLAVE #1
and press
$
to apply the change.
e. Exit the Multiple Units menu and return to main screen by pressing
$
to save the settings
upon power-up. The unit goes to REMOTE mode, the status message reads
MASTER
Module not found
, the Fault indicator is lit, and the unit continues to beep once a min-
ute until the master is found. The only function keys displayed are
!
,
#
and
%
. While
the system is running,
!
and
%
are no longer available;
#
functions normally.
TABLE 2-12. MULTIPLE UNITS MENU FUNCTIONS
SETTING
CHOICES
(
BOLD
= Factory Default)
FUNCTION
CONFIGURATION
STANDALONE
PARALLEL
SERIES
MASTER 2 X 2
MASTER 3 X 2
STANDALONE - Unit operates independently, no additional units connected.
PARALLEL - Unit to be configured for parallel operation; opens UNIT TYPE
and CONNECTION TYPE options shown below. Used when units are con-
nected in parallel (increase output current) (see NOTE below).
SERIES - Unit to be configured for series operation; opens UNIT TYPE and
CONNECTION TYPE options shown below. Used when units are connected
in series (increase output voltage) (see NOTE below).
MASTER 2 X 2 - Unit configured as master in control of two parallel branches
comprised of two series connected units. Used when units are connected in
parallel and series to double output voltage and current (see NOTE below).
MASTER 3 X 2 - Unit configured as master in control of two parallel branches
comprised of three series connected units. Used when units are connected in
parallel and series to triple output voltage and double output current (see
NOTE below).
UNIT TYPE
(for parallel and series
selections only)
STANDALONE
1
2
3
4
SLAVE #1
SLAVE #2
SLAVE #3
SLAVE #4
SLAVE #5
STANDALONE - Unit operates independently, no additional units connected.
1 - Unit is the master (controller), with one slave unit connected.
2 - Unit is the master (controller), with two slave units connected.
3 - Unit is the master (controller), with three slave units connected.
4 - Unit is the master (controller), with four slave unit connected.
SLAVE #1 - Unit is slave no. 1 in configuration using one to five slave units.
SLAVE #2 - Unit is slave no. 2 in configuration using two to five slave units.
SLAVE #3 - Unit is slave no. 3 in configuration using three to five slave units.
For Master 2X2 and Master 3X2, slave #3 is always the unit controlled in par-
allel by the master.
SLAVE #4 - Unit is slave no. 4 in configuration using four or five slave units.
SLAVE #5 - Unit is slave no. 5 in MASTER 3X2 configuration using two paral-
lel branches comprised of three series-connected units.
CONNECTION TYPE
(for parallel and series
selections only)
PARALLEL
SERIES
Not Selectable - Indicates whether parallel or series was chosen as Configu-
ration type.
Содержание BOP-MG 1KW
Страница 2: ......
Страница 10: ......
Страница 20: ...x BOP 1K 111315 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Страница 39: ...BOP HIPWR 111315 1 19 1 20 Blank FIGURE 1 3 BOP OUTPUT CHARACTERISTICS...
Страница 40: ......
Страница 56: ...2 16 BOP HIPWR 111315 FIGURE 2 5 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Страница 57: ...BOP HIPWR 111315 2 17 FIGURE 2 6 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Страница 68: ......