1-2
BOP HIPWR 111315
TABLE 1-2. BOP GENERAL SPECIFICATIONS
SPECIFICATION
RATING/DESCRIPTION
CONDITION
INPUT CHARACTERISTICS
a-c voltage
nominal
200/220/230/240Va-c
(1)
(200-240 Va-c)
No setting required. Single phase or between
2 phases of a 3-phase system within 200-
240Va-c.
range
176 - 264 Va-c
Continuous; Input voltage outside range
causes protection fault.
Frequency
nominal
50/60 Hz
range
47 - 63 Hz
Current
176 Va-c
9.5A (7.5A)
(2)
maximum
264 Va-c
6.4A (4.4A)
(2)
maximum
Power factor
Source
0.99 minimum
nominal output power
Sink
0.97 minimum
Efficiency
65% (56%)
(2)
minimum when sourcing
Switching frequency
70 KHz ±5% (50KHz ±5%)
(2)
Active PFC Input for both Source and Recu-
peration (Sink)
EMC Compliance
EN61326-1 (1997)
Class A equipment
EMC immunity to:
ESD
EN61000-4-2
Electrostatic discharge
Radiated RF
EN61000-4-3
EFT
EN61000-4-4
Electrical fast transient/burst
Surges
EN61000-4-5
Conducted RF
EN61000-4-6
EMC emissions
Conducted
EN61000-3-2
harmonics
EN61000-3-3
fluctuation & flicker
Conducted
EN55011/CISPR11
0.15 to 30 MHz
Radiated
EN55011/CISPR11
30 to 1000 MHz
Leakage current
3.5 mA
230V a-c, 47-63 Hz
Insulation coordination
Input
Installation Category II
For TN or TT power system
Overvoltage Category II
Output
Installation Category II
Maximum 300V common mode voltage
between output terminals and chassis ground.
Overvoltage Category II
Pollution degree
2
OUTPUT CHARACTERISTICS
(3)
Type of stabilizer
Voltage-current, 4-quadrant
Switch mode
Switching frequency
100KHz ±5%
Output Stage
Source adjustment
range
voltage
-100% to +100% of rating
0 to 50 deg C
current
-100% to +100% of rating
Sink adjustment range
voltage
-100% to +100% of rating
0 to 50°C, recuperated energy is sent
back into line for general reuse
current
-100% to +100% of rating
(1) All specifications listed in this table are for 230V a-c input voltage.
(2) BOP 6-125MG and BOP 10-75MG only.
(3) Output characteristics are for a single standalone unit. Output characteristics of identical multiple unit parallel/series configurations
are described in the Technical Manual associated with the applicable Cable Kit (see Table 1-4).
Содержание BOP-MG 1KW
Страница 2: ......
Страница 10: ......
Страница 20: ...x BOP 1K 111315 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Страница 39: ...BOP HIPWR 111315 1 19 1 20 Blank FIGURE 1 3 BOP OUTPUT CHARACTERISTICS...
Страница 40: ......
Страница 56: ...2 16 BOP HIPWR 111315 FIGURE 2 5 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Страница 57: ...BOP HIPWR 111315 2 17 FIGURE 2 6 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Страница 68: ......