BOP-1K 111315
B-3
B.5
INITiate[:IMMediate] COMMAND
INIT[:IMM]
Syntax:
Short Form: INIT:[IMM] Long Form: INITiate[:IMMediate]
Description:
Enables a single trigger.
This command enables a single trigger. A *TRG command completes the
sequence, however TRIG:SOUR (see PAR. B.148) must be set to BUS. Upon receipt of the *TRG
command, the power supply will return to the commanded values of voltage and current established
by the VOLT:TRIG and CURR:TRIG commands. After a *TRG command has been received, subse-
quent *TRG commands have no effect unless preceded by INIT or INIT:CONT ON. Related Com-
mands: *TRG, TRIG, TRIG:SOUR. (See example, Figure B-1.)
FIGURE B-1. PROGRAMMING THE OUTPUT
CAL:CEXT command
CAL:CGA command
CAL:CLIM command
CAL:CPR command
CAL:CURR[:DATA] command
CAL:DATA value command
CAL:DPOT command
CAL:SAVE command
CAL:STAT command and query
CAL:VEXT command
CAL:VGA command
CAL:VLIM command
CAL:VOLT[:DATA] command
CAL:VPR command
CAL:ZERO command
NOTES: 1. The power supply is assumed to be operating in constant voltage mode.
2 Examples below are intended only to illustrate command functions. Refer to PAR. 3.5.2 for pro-
gramming techniques to optimize performance.
OUTP ON
Turns the output on.
VOLT 21; CURR 1.5
Power supply output programmed to go to 21V, current limit 1.5A
INIT:CONT ON
Continuous triggers enabled.
INIT:CONT?
Power supply returns “1.”
TRIG:SOUR BUS
Prepare unit to wait for *TRG.
VOLT:TRIG 15;CURR:TRIG 3
Power supply output programmed to return to 15V, current limit
3A upon receipt of trigger.
*TRG
Power supply output returns to 15V,current limit 3A.
VOLT 21; CURR 5E-2
Power supply output programmed to go to 21V, current limit 0.05A
MEAS:VOLT?
If actual value of output voltage is 20.99V, power supply
returns 2.099E1 within the limits of readback accuracy.
MEAS:CURR?
If actual value of output current is 0.0499A, power supply
returns 4.99E-2 within the limits of readback accuracy.
FUNC:MODE CURR
Establishes constant current mode as power supply operating mode.
VOLT 21; CURR 1.1
Power supply programmed to voltage limit 21V, 1.1A.
CURR?
Returns 1.1.
FUNC:MODE VOLT
Establishes constant voltage mode as power supply operating mode.
CURR:TRIG?
Returns 3 (current value established by CURR:TRIG).
VOLT:TRIG?
Returns 15 (voltage value established by VOLT:TRIG).
*TRG
Power supply output returns to 15V, current limit 3A.
INIT:CONT 0
Triggers disabled.
INIT:CONT?
Power supply returns “0.”
VOLT 0
Power supply output programmed to go to 0V.
MEAS:VOLT?
Returns 0 within the limits of readback accuracy (measured output
voltage).
VOLT?
Returns 0 within the limits of readback accuracy (programmed output
voltage).
CURR?
Returns 3 (programmed current).
MEAS:CURR?
Returns 0 within the limits of readback accuracy (measured output
current).
Содержание BOP-MG 1KW
Страница 2: ......
Страница 10: ......
Страница 20: ...x BOP 1K 111315 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Страница 39: ...BOP HIPWR 111315 1 19 1 20 Blank FIGURE 1 3 BOP OUTPUT CHARACTERISTICS...
Страница 40: ......
Страница 56: ...2 16 BOP HIPWR 111315 FIGURE 2 5 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Страница 57: ...BOP HIPWR 111315 2 17 FIGURE 2 6 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Страница 68: ......