GD200A series VFD
Function parameters
-73-
Function
code
Name
Description
Default
value
Modify
P07.53 Bus voltage at the last but one fault
0.0V
●
P07.54 The max. temperature at the last but one fault
0.0°C
●
P07.55 Input terminals state at the last but one fault
0
●
P07.56 Output terminals state at the last but one fault
0
●
P08 Group Enhanced function
Function
code
Name
Description
Default
value
Modify
P08.00
ACC time 2
Refer to
Goodrive200A series define four groups of
ACC/DEC time which can be selected by P5
group. The first group of ACC/DEC time is the
factory default one.
Setting range: 0.0
–3600.0s
Depend
on
model
○
P08.01
DEC time 2
Depend
on
model
○
P08.02
ACC time 3
Depend
on
model
○
P08.03
DEC time 3
Depend
on
model
○
P08.04
ACC time 4
Depend
on
model
○
P08.05
DEC time 4
Depend
on
model
○
P08.06
Jogging
frequency
This parameter is used to define the reference
frequency during jogging.
Setting range: 0.00Hz
–P00.03 (the max.
frequency)
5.00Hz
○
P08.07
Jogging ACC
time
The jogging ACC time means the time needed if
the VFD runs from 0Hz to the max. frequency.
The jogging DEC time means the time needed if
the VFD goes from the max. frequency (P00.03) to
0Hz.
Setting range: 0.0
–3600.0s
Depend
on
model
○
P08.08
Jogging DEC
time
Depend
on
model
○
P08.09
Jumping
frequency 1
When the set frequency is in the range of jumping
frequency, the VFD will run at the edge of the
jumping frequency.
The VFD can avoid the mechanical resonance
point by setting the jumping frequency. The VFD
0.00Hz
○
P08.10
Jumping
frequency
range 1
0.00Hz
○