GD200A series VFD
Function parameters
-60-
Function
code
Name
Description
Default
value
Modify
Sln
FWD
REV
Direction
ON
OFF→
ON
ON
Forward
OFF
Reverse
ON
ON
OFF→
ON
Forward
OFF
Reverse
ON→
OFF
/
/
Decelerate
to stop
/
/
Note
: for the 2-wire running mode, when
FWD/REV terminal is valid, the VFD stop because
of the stopping command from other sources,
even the control terminal FWD/REV keeps valid;
the VFD won’t work when the stopping command
is canceled. Only when FWD/REV is relaunched,
the VFD can start again. For example, the valid
STOP/RST stop when PLC signal cycles stop,
fixed-length stop and terminal control (see
P05.14
S1 terminal
switching-on
delay time
The function code defines the corresponding
delay time of electrical level of the programmable
terminals from switching on to switching off.
Si electrical level
Si valid
invalid
invalid
Switcn-on
delay
Switcn-off
delay
valid
Setting range: 0.000
–50.000s
0.000s
○
P05.15
S1 terminal
switching-off
delay time
0.000s
○
P05.16
S2 terminal
switching-on
delay time
0.000s
○
P05.17
S2 terminal
switching-off
delay time
0.000s
○
P05.18
S3 terminal
switching-on
delay time
0.000s
○
P05.19
S3 terminal
switching-off
delay time
0.000s
○
P05.20
S4 terminal
switching-on
delay time
0.000s
○