GD200A series VFD
Function parameters
-77-
Function
code
Name
Description
Default
value
Modify
Setting range of
: 0.0
–100.0%
(FDT2 electrical level)
P08.36
Amplitude
value for
frequency
arrival
detection
When the output frequency is among the below or
above range of the set frequency, the
multi-function digital output terminal will output the
signal of "frequency arrival", see the diagram
below for detailed information:
Y
RO1, RO2
,
Output frequency
Detecting range
T
T
The setting range: 0.00Hz
–P00.03
(the max. frequency)
0.00 Hz
○
P08.37
Energy braking
enable
This parameter is used to control the internal
braking unit.
0: Disable
1: Enable
Note:
Only applicable to the models with internal
braking units.
0
○
P08.38
Threshold
voltage
After setting the original bus voltage, adjust this
parameter to break the load appropriately. The
factory value changes with voltage level.
Setting range: 200.0
–2000.0V
For 220V:
380.0V
○
For 380V:
700.0V
For 660V:
1120.0V
P08.39
Cooling fan
running mode
Set the operation mode of the cooling fan.
0: Normal mode, after the rectifier receives
operation command or the detected temperature
of module is above 45°C or the module current is
above 20% of the rated current, the fan rotates.
1: The fan keeps on running after power on
(generally for the site with high temperature and
humidity)
2: The fan will start when the ramp frequency of
the VFD is larger than 0Hz; if the running
frequency is 0Hz or changes from running state to
stop state, the fan will stop after one minute.
Setting range: 0
–2
0
○