GD200A series VFD
Communication protocol
-134-
The RTU request command is:
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR
01H
CMD
08H
High bit of sub-function code
00H
Low bit of sub-function code
00H
High bit of data content
12H
Low bit of data content
ABH
Low bit of CRC
ADH
High bit of CRC
14H
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
The RTU response command is:
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR
01H
CMD
08H
High bit of sub-function code
00H
Low bit of sub-function code
00H
High bit of data content
12H
Low bit of data content
ABH
Low bit of CRC
ADH
High bit of CRC
14H
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
9.4.1.4 Command code: 10H, continuous writing
Command code 10H means that if the master writes data to the VFD, the data number depends on
the "data number" in the command code. The max. continuous reading number is 16.
For example, write 5000(1388H) to 0004H of the VFD whose slave address is 02H and 50(0032H)
to 0005H, the frame structure is as below:
The RTU request command is:
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR
02H
CMD
10H
High bit of write data
00H
Low bit of write data
04H
High bit of data number
00H
Low bit of data number
02H
Byte number
04H
High bit of data 0004H
13H