GD200A series VFD
Function parameters
-78-
Function
code
Name
Description
Default
value
Modify
P08.40 PWM selection
0x00
–0x21
LED ones: PWM mode selection
0: PWM mode 1, three-phase modulation and
two-modulation
1: PWM mode 2, three-phase modulation
LED tens: low-speed carrier frequency limit mode
0: Low-speed carrier frequency limit mode 1, the
carrier frequency will limit to 2k if it exceeds 2k at
low speed
1: Low-speed carrier frequency limit mode 2, the
carrier frequency will limit to 4k if it exceeds 4k at
low speed
2: No limit
00
◎
P08.41
Over
modulation
selection
0x00
–0x11
LED ones
0: Invalid
1: Valid
LED tens
0: Light overmodulation
1: Heavy overmodulation
0x01
◎
P08.42
Keypad data
control
0x000
–0x1223
LED ones: frequency enable selection
0: Both
∧
/
∨
keys and digital potentiometer
adjustments are valid
1: Only
∧
/
∨
keys adjustment is valid
2: Only digital potentiometer adjustments is valid
3: Neither
∧
/
∨
keys nor digital potentiometer
adjustments are valid
LED tens: frequency control selection
0: Only valid when
1: Valid for all frequency setting manner
2: Invalid for multi-step speed when multi-step
speed has the priority
LED hundreds: action selection during stopping
0: Setting is valid
1: Valid during running, cleared after stopping
2: Valid during running, cleared after receiving the
stop command
LED thousands:
∧
/
∨
keys and digital
0x0000
○