GD200A series VFD
Function parameters
-46-
Function
code
Name
Description
Default
value
Modify
P01.24
Delay time of
the stop speed
P01.24
In running
T
Output frequency
Stop speed
Setting range: 0.0
–100.0 s
0.0s
●
P01.25
0Hz output
selection
0: Output without voltage
1: Output with voltage
2: Output at the DC braking current
0
●
P02 Group Motor 1
Function
code
Name
Description
Default
value
Modify
P02.01
Rated power of
AM 1
0.1
–3000.0kW
To ensure control performance,
set
according to
the AM nameplate.
Goodrive200A provides the
parameter self-learning function.
Accurate parameter self-learning
is based on the correct settings of
motor nameplate parameters.
Perform motor configuration
according to the mapping
between VFDs and motors. If the
motor power is far from the power
of the motor that matches the
VFD, the control performance of
the VFD deteriorates sharply.
Note:
Resetting the rated motor
power (
) will initialize
Depend
on
model
◎
P02.02
Rated
frequency of
AM 1
0.01Hz
(the max.
frequency)
50.00
Hz
◎
P02.03
Rated speed of
AM 1
1
–36000rpm
Depend
on
model
◎
P02.04
Rated voltage
of AM 1
0
–1200V
Depend
on
model
◎
P02.05
Rated current
of AM 1
0.8
–6000.0A
Depend
on
model
◎
P02.06
Stator resistor
of AM 1
0.001
–65.535Ω
After motor parameter
self-learning is completed
successfully, in rotary
self-learning and static
self-learning 1, the settings of
Depend
on
model
○
P02.07
Rotor resistor
of AM 1
0.001
–65.535Ω
Depend
on
model
○