GD200A series VFD
Function parameters
-58-
Function
code
Name
Description
Default
value
Modify
Set the bit to 1, the input terminal is cathode.
BIT0
BIT1
BIT2
BIT3
BIT4
S1
S2
S3
S4
S5
BIT5
BIT6
BIT7
BIT8
S6
S7
S8
HDI
The setting range: 0x000
–0x1FF
P05.11
ON-OFF filter
time
Set the sample filter time of S1
–S8 and HDI
terminals. If the interference is strong, increase
the parameter to avoid the disoperation.
0.000
–1.000s
0.010s
○
P05.12
Virtual
terminals
setting
0x000
–0x1FF(0: Disabled, 1: Enabled )
BIT0: S1
virtual terminal
BIT1: S2
virtual terminal
BIT2: S3
virtual terminal
BIT3: S4
virtual terminal
BIT4: S5
virtual terminal
BIT5: S6
virtual terminal
BIT6: S7
virtual terminal
BIT7: S8
virtual terminal
BIT8: HDI
virtual terminal
Note:
After a virtual terminal is enabled, the
terminal status can be changed only through
communication, and the communication address
is 0x200A.
0x000
◎
P05.13
Terminals
control running
mode
Set the operation mode of the terminals control
0: 2-wire control 1, comply the enable with the
direction. This mode is widely used. It determines
the rotation direction by the defined FWD and
REV terminals command.
FWD
REV
COM
K1
K2
Running
command
FWD
REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Stopping
Hold on
Forward
running
Reverse
running
1: 2-wire control 2; Separate the enable from the
direction. FWD defined by this mode is the
enabling ones. The direction depends on the state
of the defined REV.
0
◎