GD200A series VFD
Function parameters
-70-
Function
code
Name
Description
Default
value
Modify
BIT7: linear speed
BIT8: AC inlet current (A on)
BIT9: upper limit frequency (Hz on)
P07.07
The parameter
in the stop state
0x0000
–0xFFFF
BIT0: set frequency
(Hz on, frequency flickering slowly)
BIT1: bus voltage (V on)
BIT2: input terminals state
BIT3: output terminals state
BIT4: PID reference (% flickering)
BIT5: PID feedback value (% flickering)
BIT6: reserved
BIT7: analog AI1 value (V on) (implemented
through the analog potentiometer on the keypad
for the 0150G/018P and lower models; not
available for the 018G/022P and higher models.)
BIT8: analog AI2 value (V on)
BIT9: analog AI3 value (V on)
BIT10: high speed pulse HDI frequency
BIT11: PLC and the current step in multi-step
speed
BIT12: pulse counters
BIT14: upper limit frequency (Hz on)
0x00FF
○
P07.08
Frequency
coefficient
0.01
–10.00
Displayed frequency=running frequency*
1.00
○
P07.09
Rotation speed
coefficient
0.1
–999.9%
Mechanical rotation speed =120*displayed
running frequency×
/motor pole pairs
100.0%
○
P07.10
Linear speed
coefficient
0.1
–999.9%
Linear speed= Mechanical rotation speed×
1.0%
○
P07.11
Rectifier bridge
module
temperature
0
–100.0°C
/
●
P07.12
IGBT module
temperature
0
–100.0°C
/
●
P07.13
Software
version
1.00
–655.35
/
●
P07.14
Local
accumulative
running time
0
–65535h
/
●