GD200A series VFD
Function parameters
-90-
Function
code
Name
Description
Default
value
Modify
0: Valid
1: Invalid
Setting range of
: 50.0
–200.0%
Setting range of
: 0.00
–50.00Hz/s
P11.08
Overload
pre-alarm of
The output current of the VFD or the motor is
above
and the lasting time is beyond
, overload pre-alarm will be output.
Output current
Overload
pre-alarm
point
T
T
Y,
RO1, RO2
Pre-alarm
time
Pre-alarm
time
Setting range of
Enable and define the overload pre-alarm of the
VFD or the motor.
LED ones:
0: Overload pre-alarm of the motor, comply with
the rated current of the motor
1: Overload pre-alarm of the VFD, comply with the
rated current of the VFD
LED tens:
0: The VFD continues to work after underload
pre-alarm
1: The VFD continues to work after underload
pre-alarm and the VFD stops running after
overload fault
2: The VFD continues to work after overload
pre-alarm and the VFD stops running after
underload fault
3. The VFD stops when overload or underload.
LED hundreds :
0: Detection all the time
1: Detection in constant running
LED thousands: Overload integral selection
0: Overload integral is invalid
0x000
○
P11.09
Overload
pre-alarm test
level
G type:
150%
○
P type:
120%
P11.10
Overload
pre-alarm
detection time
0x0000
○