GD200A series VFD
Peripheral options and parts
-167-
motor insulator, compensation must be made by adding an output reactor. When a VFD is used to
drive multiple motors, take the total length of the motor cables (that is, sum of the lengths of the
motor cables) into account. When the total length is longer than 50 m, an output reactor must be
added on the output side of the VFD. If the distance between the VFD and motor ranges from 50 m
to 100 m, select the reactor according to the following table. If the distance is longer than 100 m,
contact INVT's technical support. The mapping between VFD models and reactors is as follows:
VFD model
Input reactor
DC reactor
Output reactor
GD200A-0R7G-4
ACL2-1R5-4
/
OCL2-1R5-4
GD200A-1R5G-4
ACL2-1R5-4
/
OCL2-1R5-4
GD200A-2R2G-4
ACL2-2R2-4
/
OCL2-2R2-4
GD200A-004G/5R5P-4
ACL2-004-4
/
OCL2-004-4
GD200A-5R5G/7R5P-4
ACL2-5R5-4
/
OCL2-5R5-4
GD200A-7R5G/011P-4
ACL2-7R5-4
/
OCL2-7R5-4
GD200A-011G/015P-4
ACL2-011-4
/
OCL2-011-4
GD200A-015G/018P-4
ACL2-015-4
/
OCL2-015-4
GD200A-018G/022P-4
ACL2-018-4
/
OCL2-018-4
GD200A-022G/030P-4
ACL2-022-4
/
OCL2-022-4
GD200A-030G/037P-4
ACL2-037-4
/
OCL2-037-4
GD200A-037G/045P-4
ACL2-037-4
DCL2-037-4
OCL2-037-4
GD200A-045G/055P-4
ACL2-045-4
DCL2-045-4
OCL2-045-4
GD200A-055G/075P-4
ACL2-055-4
DCL2-055-4
OCL2-055-4
GD200A-075G/090P-4
ACL2-075-4
DCL2-075-4
OCL2-075-4
GD200A-090G/110P-4
ACL2-110-4
DCL2-090-4
OCL2-110-4
GD200A-110G/132P-4
ACL2-110-4
DCL2-132-4
OCL2-110-4
GD200A-132G/160P-4
ACL2-160-4
DCL2-132-4
OCL2-160-4
GD200A-160G/185P-4
ACL2-160-4
DCL2-160-4
OCL2-200-4
GD200A-185G/200P-4
ACL2-200-4
DCL2-220-4
OCL2-200-4
GD200A-200G/220P-4
ACL2-200-4
DCL2-220-4
OCL2-200-4
GD200A-220G/250P-4
ACL2-280-4
DCL2-280-4
OCL2-280-4
GD200A-250G/280P-4
ACL2-280-4
DCL2-280-4
OCL2-280-4
GD200A-280G/315P-4
ACL2-280-4
DCL2-280-4
OCL2-280-4
GD200A-315G/355P-4
ACL2-350-4
DCL2-315-4
OCL2-350-4
GD200A-355G/400P-4
Standard
DCL2-400-4
OCL2-350-4
GD200A-400G-4
Standard
DCL2-400-4
OCL2-400-4
GD200A-450G-4
Standard
DCL2-500-4
OCL2-500-4
GD200A-500G-4
Standard
DCL2-500-4
OCL2-500-4
Note:
1. The rated derate voltage of the input reactor is 2%±15%.
2. The power factor of the input side is above 90% after adding DC reactor.