GD200A series VFD
Installation guidelines
-14-
Environment
Conditions
Storage temperature
-30 to +60°C
Running environment
condition
The installation site of the VFD should meet the following
requirements.
Away from the electromagnetic radiation source;
Away from contaminative air, such as corrosive gas, oil mist and
flammable gas;
Ensure foreign objects, such as metal power, dust, oil, water cannot
enter into the VFD (do not install the VFD on the flammable materials
such as wood);
Away from direct sunlight, oil mist, steam and vibration environment.
Altitude
Below 1000 meters
When the installation site altitude exceeds 1000m, derate 1% for every
increase of 100m; when the installation site altitude exceeds 3000m,
consult the local INVT dealer or office.
Vibration
≤ 5.8m/s
2
(0.6g)
Installation direction
The VFD should be installed on an upright position to ensure sufficient
cooling effect.
Note:
Goodrive200A series VFDs should be installed in a clean and ventilated environment
according to enclosure classification.
Cooling air must be clean, free from corrosive materials and electrically conductive dust.
4.2.2 Installation direction
The VFD may be installed on the wall or in a cabinet.
The VFD must be installed in an upright position. Check the installation site according to the
requirements below. For frame details, please see Appendix B Dimension drawings.
A Vertical installation
B Horizontal installation
C Transversal installation
OK
NG
NG
Figure 4-1 Installation direction of the VFD