GD200A series VFD
Fault tracking
-123-
Checking part
Checking item
Checking
method
Criterion
Terminals
seat
Ensure
that
there
is
no
damage
Visual
examination
NA
Filter
capacitors
Ensure
that
there
is
no
weeping,
color-changing,
crackles and cassis expansion.
Visual
examination
NA
Ensure the safety valve is in
the right place.
Estimate
the
usage
time
according to the
maintenance
or
measure the static
capacity.
NA
If necessary, measure the
static capacity.
Measure
the
capacity
by
instruments.
The static capacity is
above or equal to the
original value *0.85.
Resistors
Ensure
whether
there
is
replacement
and
splitting
caused by overheating.
Smelling
and
visual
examination
NA
Ensure that there is no offline.
Visual
examination
or
remove
one
ending
to
coagulate
or
measure
with
multimeters
The resistors are in
±10% of the standard
value.
Transformers
and reactors
Ensure there is no abnormal
vibration, noise and smelling,
Hearing, smelling
and
visual
examination
NA
Electromag-
netism
contactors
and relays
Ensure
whether
there
is
vibration
noise
in
the
workrooms.
Hearing
NA
Ensure the contactor is good
enough.
Visual
examination
NA
Control
circuit
PCB and
plugs
Ensure there are no loose
screws and contactors.
Fasten up
NA
Ensure there is no smelling
and color-changing.
Smelling
and
visual
examination
NA
Ensure there are no crackles,
damage distortion and rust.
Visual
examination
NA