GD200A series VFD
Function parameters
-93-
Function
code
Name
Description
Default
value
Modify
7: Even check (E,7,1) for ASCII
8: Odd check (O,7,1) for ASCII
9: No check (N,7,2) for ASCII
10: Even check (E,7,2) for ASCII
11: Odd check (O,7,2) for ASCII
12: No check (N,8,1) for ASCII
13: Even check (E,8,1) for ASCII
14: Odd check (O,8,1) for ASCII
15: No check (N,8,2) for ASCII
16: Even check (E,8,2) for ASCII
17: Odd check (O,8,2) for ASCII
P14.03
Response
delay
0
–200ms
It means the interval time between the interval
time when the drive receive the data and sent it to
the upper monitor. If the answer delay is shorter
than the system processing time, then the answer
delay time is the system processing time, if the
answer delay is longer than the system processing
time, then after the system deal with the data,
waits until achieving the answer delay time to
send the data to the upper monitor.
5
○
P14.04
Fault time of
communication
overtime
0.0 (invalid), 0.1
–60.0s
When the function code is set as 0.0, the
communication overtime parameter is invalid.
When the function code is set as non-zero, if the
interval time between two communications
exceeds the communication overtime, the system
will report "485 communication faults" (CE).
Generally, set it as invalid; set the parameter in
the continuous communication to monitor the
communication state.
0.0s
○
P14.05
Transmission
fault processing
0: Alarm and stop freely
1: No alarm and continue to run
2: No alarm and stop according to the stop means
(only under the communication control)
3: No alarm and stop according to the stop means
(under all control modes)
0
○
P14.06
Communication
processing
LED ones place:
0: Operation with response: the drive will respond
0x00
○