Function parameters
-89-
Function
code
Name
Description
Default
value
Modify
P11.03
Overvoltage
stall protection
0: Disable
1: Enable
DC bus voltage
Overvoltage stall
point
Output frequency
1
○
P11.04
Protection
voltage at
overvoltage
stall
120
–150%(standard bus voltage) (380V)
136%
○
120
–150%(standard bus voltage) (220V)
120%
P11.05
Current limit
action selection
The actual increasing ratio is less than the ratio of
output frequency because of the big load during
ACC running. It is necessary to take measures to
avoid overcurrent fault and the VFD trips.
During the running of the VFD, this function will
detect the output current and compare it with the
limit defined in
. If it exceeds the level, the
VFD will run at stable frequency in ACC running,
or the VFD will derate to run during the constant
running. If it exceeds the level continuously, the
output frequency will keep on decreasing to the
lower limit. If the output current is detected to be
lower than the limit level, the VFD will accelerate
to run.
Output frequency
Output current
Limiting
point
Setting
frequency
ACC
Constant
speed
T
T
Setting range of
0x00
–0x11
LED ones: current limit
0: Invalid
1: Always valid
LED tens: overload alarm
01
◎
P11.06
Automatic
current limit
G type:
160.0%
◎
P type:
120.0%
P11.07
The decreasing
ratio during
current limit
10.00
Hz/s
◎