GD200A series VFD
Function parameters
-34-
that the users cannot modify the factory parameters by themselves, otherwise, if the parameter
setting is incorrect, damage to the VFD may occur). If the password protection is unlocked, the user
can modify the password freely and the VFD will work as the last setting one. When P07.00 is set to
0, the password can be canceled. If P07.00 is not 0 during powering on, then the parameter is
protected by the password. When modify the parameters by serial communication, the function of
the password follows the above rules, too.
P00 Group Basic functions
Function
code
Name
Description
Default
value
Modify
P00.00
Speed control
mode
1: Sensorless vector control mode 1 (applying to
AM)
No need to install encoders. It is suitable in cases
with high speed control accuracy for accurate
speed and torque control at all power ratings.
2: SVM control
No need to install encoders. It can improve the
control accuracy with the advantages of stable
operation, valid low-frequency torque boost and
current vibration suppression and the functions of
slip compensation and voltage adjustment.
Note
: AM-Asynchronous motor
2
◎
P00.01
Run command
channel
Select the run command channel of the VFD.
The control command of the VFD includes: start,
stop, forward, reverse, jogging and fault reset.
0: Keypad running command
channel("LOCAL/REMOT" light off)
Carry out the command control by RUN,
STOP/RST on the keypad.
Set the multi-function key QUICK/JOG as
FWD/REV shifting function (
=3) to change
the running direction; press
RUN
and
STOP/RST
simultaneously in running state to make the VFD
coast to stop.
1: Terminal running command channel
("LOCAL/REMOT" flickering)
Carry out the running command control by the
forward rotation, reverse rotation and forward
jogging and reverse jogging of the multi-function
terminals
2: Communication running command channel
("LOCAL/REMOT" on);
0
○