GD200A series VFD
Function parameters
-76-
Function
code
Name
Description
Default
value
Modify
P08.27
Set running
time
Pre-set running time of the VFD. When the
accumulative running time achieves the set time,
the multi-function digital output terminals will
output the signal of "running time arrival".
Setting range: 0
–65535 min
0m
○
P08.28
Fault reset
times
The time of the fault reset: set the fault reset time
by selecting this function. If the reset time exceeds
this set value, the VFD will stop for the fault and
wait to be repaired.
The interval time of the fault reset: The interval
between the time when the fault occurs and the
time when the reset action occurs.
Setting range of
: 0
–10
Setting range of
: 0.1
–3600.0s
0
○
P08.29
Interval time of
automatic fault
reset
1.0s
○
P08.30
Frequency
decreasing
ratio of the
dropping
control
The output frequency of the VFD changes as the
load. And it is mainly used to balance the power
when several VFDs drive one load.
Setting range: 0.00
–10.00Hz
0.00Hz
○
P08.32
FDT1 electrical
level detection
value
When the output frequency exceeds the
corresponding frequency of FDT electrical level,
the multi-function digital output terminals will
output the signal of "frequency level detect FDT"
until the output frequency decreases to a value
lower than (FDT electrical level
—FDT retention
detection value) the corresponding frequency, the
signal is invalid. Below is the waveform diagram:
Output frequency
FDT level
Y,
RO1, RO2
FDT lag
Setting range of
: 0.00Hz
–P00.03
(the max. frequency)
Setting range of
: 0
–100.0%
(FDT1 electrical level)
Setting range of
: 0.00 Hz
–P00.03
(the max. frequency)
50.00
Hz
○
P08.33
FDT1 retention
detection value
5.0%
○
P08.34
FDT2 electrical
level detection
value
50.00
Hz
○
P08.35
FDT2 retention
detection value
5.0%
○