GD200A series VFD
Function parameters
-36-
Function
code
Name
Description
Default
value
Modify
configuration, of which AI1/AI2 are the
voltage/current option (0 (2)
–10V/0 (4)–20mA)
which can be shifted by jumpers; while AI3 is
voltage input (-10V
–+10V).
Note:
When analog AI1/AI2 selects 0 (4)
–20mA
input, the corresponding voltage of 20mA is 10V.
100.0% of the analog input setting corresponds to
the maximum frequency (function code
) in
forward direction and -100.0% corresponds to the
maximum frequency in reverse direction
(function code
4: High-speed pulse HDI setting
The frequency is set by high-speed pulse
terminals. Goodrive200A series VFDs provide 1
channel high speed pulse input as the standard
configuration. The pulse frequency range is
0.00
–50.00kHz.
100.0% of the high speed pulse input setting
corresponds to the maximum frequency in forward
direction (
) and -100.0% corresponds to
the maximum frequency in reverse direction
Note:
The pulse setting can only be input by
multi-function terminals HDI. Set
input selection) to high speed pulse input.
5: Simple PLC program setting
The VFD runs at simple PLC program mode when
=5. Set P10 (simple PLC and
multi-step speed control) to select the running
frequency, running direction, ACC/DEC time and
the keeping time of corresponding step. See the
function description of P10 for detailed
information.
6: Multi-step speed running setting
The VFD runs at multi-step speed mode when
=6. Set P05 to select the
current running step, and set P10 to select the
current running frequency.
The multi-step speed has the priority when