Table 6. Firmware Error Codes. (continued)
Error
Code
Description
Action/ Possible Failing FRU
25Cyy003 PD bits are
miss-matched or
missing one memory
module.
1. Make sure both memory modules in the pair are the same type.
2. Replace System Planar.
See “Memory PD Bits” on page 98 for definition of
″
yy
″
.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
25Cyy004 Memory modules are
disabled.
Remove the unused memory module. Ensure both cluster bays have the same
amount of memory after the repair is complete. Use the service terminal Install
Remove Menu, Cluster Memory Menu, List Installed Memory option.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
25Cyy005 Memory module failed
address test.
1. Replace memory module.
2. Replace memory card.
3. Replace System Planar.
4. Remove the CPU card in P1–C2 (farthest away from the memory cards). If
the problem is resolved, replace the removed CPU card. If not, continue.
5. Exchange the CPU card in P1–C1 (closest to the memory cards) with the
CPU card removed in step one. If the problem is resolved, replace the
removed CPU card. If not, continue.
6. Return both CPU cards to their original slots.
See “Memory PD Bits” on page 98 for definition of
″
yy
″
.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
25Cyy006 Memory module failed
inter-extent test.
1. Replace system planar.
2. Remove the CPU card in P1–C2 (farthest away from the memory cards). If
the problem is resolved, replace the removed CPU card. If not, continue.
3. Exchange the CPU card in P1–C1 (closest to the memory cards) with the
CPU card removed in step one. If the problem is resolved, replace the
removed CPU card. If not, continue.
4. Return both CPU cards to their original slots.
See “Memory PD Bits” on page 98 for definition of
″
yy
″
.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
25Cyy007 Memory module failed
extent access test.
1. Replace system Planar.
2. Replace CPU card.
See “Memory PD Bits” on page 98 for definition of
″
yy
″
.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
25Cyy008 Memory module has
been deconfigured.
Swap the memory module with the other memory module of the same pair. Look
for any new error code.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
2602000x The I/O planar PCI slot
cannot recognize the
card plugged into the
slot.
Either the card is failing/missing or the I/O planar is failing.
Replace the card in the slot or the I/O planar until it no longer fails.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
Codes
Error Messages, Diagnostic Codes, and Service Reports, CHAPTER 9
79
Содержание E10
Страница 2: ......
Страница 68: ...52 VOLUME 3 ESS Service Guide...
Страница 192: ...2105 Exception Symptom Codes 176 VOLUME 3 ESS Service Guide...
Страница 198: ...Translation 182 VOLUME 3 ESS Service Guide...
Страница 256: ...CPI Diagnostic Progress Code Stop 240 VOLUME 3 ESS Service Guide...
Страница 257: ...CPI Diagnostic Progress Code Stop Appendix C Isolating a CPI Diagnostic Progress Code Stop 241...
Страница 258: ...CPI Diagnostic Progress Code Stop 242 VOLUME 3 ESS Service Guide...
Страница 259: ...Glossary of Terms and Abbreviations Copyright IBM Corp 1999 2000 243...
Страница 277: ......
Страница 278: ...Printed in the United States of America on recycled paper containing 10 recovered post consumer fiber SY27 7609 06...
Страница 279: ...Spine information Enterprise Storage Server VOLUME 3 ESS Service Guide...