Table 6. Firmware Error Codes. (continued)
Error
Code
Description
Action/ Possible Failing FRU
40A00000
(F10/F20)
System firmware IPL
failure.
1. Remove the CPU card in the C2 slot (farthest away from the memory cards).
If the problem is resolved, replace the removed CPU card. If not, continue.
2. Exchange the CPU card in the C1 slot (closest to the memory cards) with
the CPU card removed in step one. If the problem is resolved, replace the
failing CPU card.
3. System Planar (model F10/F20 only).
4. Replace I/O Planar.
5. Replace the Service Processor Card (E10/E20 only).
The F10/F20 I/O planar includes the service processor.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
40B00000 The operating system
surveillance interval
exceeded.
See 40A00000
40B00100 Surveillance time-out
on CPU 1.
Replace the CPU card in slot P1–C1 (closest to memory cards).
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
40B00101 Surveillance time-out
on CPU 2.
Refer to the actions in error code 40B00100.
40B00102 Surveillance time-out
on CPU 3.
Replace the CPU card in slot P1-C2 (farthest away from the memory cards).
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
40B00103 Surveillance time-out
on CPU 4.
Refer to the actions in error code 40B00102.
40D00003 An unknown slow
shutdown commanded.
1. Critical cooling problem. Check to ensure the customer air temperature is in
the proper range.
2. Use the service terminal to display and repair any related power problems.
Connect the service terminal to the working cluster bay and use the Repair
Menu, Shoe / Repair Problems Needing Repair option.
40D00004 An unknown fast
shutdown commanded.
Locked fan failure detected. See the action for error code 2BA00300.
40D00101 BIST on I/O Planar
failed.
Replace the I/O Planar.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
40D00102 BIST on System
Planar failed.
Replace the System Planar.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
45800000 Memory controller
check-stop.
Replace the System Planar.
If the problem is not resolved, go to
″
MAP 4540: Cluster Minimum Configuration
″
in chapter 3 of the Enterprise Storage Server Service Guide, Volume 1.
45B00001 A non-compatible
memory card is
detected.
Replace the memory card, as indicated by the physical location code.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
Codes
Error Messages, Diagnostic Codes, and Service Reports, CHAPTER 9
93
Содержание E10
Страница 2: ......
Страница 68: ...52 VOLUME 3 ESS Service Guide...
Страница 192: ...2105 Exception Symptom Codes 176 VOLUME 3 ESS Service Guide...
Страница 198: ...Translation 182 VOLUME 3 ESS Service Guide...
Страница 256: ...CPI Diagnostic Progress Code Stop 240 VOLUME 3 ESS Service Guide...
Страница 257: ...CPI Diagnostic Progress Code Stop Appendix C Isolating a CPI Diagnostic Progress Code Stop 241...
Страница 258: ...CPI Diagnostic Progress Code Stop 242 VOLUME 3 ESS Service Guide...
Страница 259: ...Glossary of Terms and Abbreviations Copyright IBM Corp 1999 2000 243...
Страница 277: ......
Страница 278: ...Printed in the United States of America on recycled paper containing 10 recovered post consumer fiber SY27 7609 06...
Страница 279: ...Spine information Enterprise Storage Server VOLUME 3 ESS Service Guide...