Table 9. Bus SRN to FRU Reference Table (Models F10/F20 Only)
SRN
Bus Identification
Possible Failing Device and AIX Location
Code
Associated FRU
9CC-100
PCI Bus 00
Internal SCSI port 1 (10-60)
I/O Planar (See notes
on 72)
Internal Ethernet port (10-80)
I/O Planar (See notes
on 72)
Device installed in I/O Slot K3 (10-68 to 10-6F)
SSA Device Card
Device installed in I/O Slot K4 (10-70 to 10-77)
SSA Device Card
9CC-101
PCI Bus 01
Device installed in I/O Slot K1 (20-58 to 20-5F)
SSA Device Card
Device installed in I/O Slot K2 (20-60 to 20-67)
SSA Device Card
9CC-102
PCI Bus 02
Internal/External SCSI port 2 (30-58)
I/O Planar. (See notes
on 72)
Device installed in I/O Slot I7 (30-68 to 30-6F)
NVS Card
Device installed in I/O Slot I8 (30-70 to 30-77)
I/O Attachment Card
9CC-103
PCI Bus 03
Device installed in I/O Slot I5 (40-58 to 40-5F)
I/O Attachment Card
Device installed in I/O Slot I6 (40-60 to 40-67)
NVS Card
651-730
ISA Bus
Diskette Drive port/device (01-D1-00-00)
I/O Planar
Parallel port/device (01-R1)
I/O Planar
Serial ports (1-3)/device (01-S1 to 01-S3)
I/O Planar
Mouse port/device (01-K1-01-00)
I/O Planar
Key-Planar port/device (01-K1-00-00)
I/O Planar
Device installed in I/O Slot 8I (01-01 or 01-02)
I/O Planar
Device installed in I/O Slot 9I (01-01 or 01-02)
I/O Planar
Checkpoints
Checkpoints are intended to let users and service support representative know what the server is doing,
with some detail, as it initializes. These checkpoints are not intended to be error indicators, but in some
cases a server could hang at one of the checkpoints without displaying an 8-character error code. It is for
these hang conditions, only, that any action should be taken with respect to checkpoints. The most
appropriate action is included with each checkpoint.
Before taking actions listed with a checkpoint, it is a good idea to look for better symptoms in the Service
Processor error log. See “Appendix A. Service Processor Operation Connection” on page 209.
SP Checkpoints
Service Processor checkpoints are in the range E010 to E0FF. The message OK indicates successful
service processor testing and initialization. Firmware checkpoints are listed in “Firmware Checkpoints” on
page 105.
To replace listed FRUs, connect the service terminal to the working cluster and then use the Repair Menu,
Replace A FRU options.
Notes:
1. If no FRUs are listed or you have replaced the listed FRUs and the problem is still not corrected, go to
″
MAP 4540: Cluster Minimum Configuration
″
in chapter 3 of the Enterprise Storage Server Service
Guide, Volume 1.
Codes
100
VOLUME 3, ESS Service Guide
Содержание E10
Страница 2: ......
Страница 68: ...52 VOLUME 3 ESS Service Guide...
Страница 192: ...2105 Exception Symptom Codes 176 VOLUME 3 ESS Service Guide...
Страница 198: ...Translation 182 VOLUME 3 ESS Service Guide...
Страница 256: ...CPI Diagnostic Progress Code Stop 240 VOLUME 3 ESS Service Guide...
Страница 257: ...CPI Diagnostic Progress Code Stop Appendix C Isolating a CPI Diagnostic Progress Code Stop 241...
Страница 258: ...CPI Diagnostic Progress Code Stop 242 VOLUME 3 ESS Service Guide...
Страница 259: ...Glossary of Terms and Abbreviations Copyright IBM Corp 1999 2000 243...
Страница 277: ......
Страница 278: ...Printed in the United States of America on recycled paper containing 10 recovered post consumer fiber SY27 7609 06...
Страница 279: ...Spine information Enterprise Storage Server VOLUME 3 ESS Service Guide...