Table 6. Firmware Error Codes. (continued)
Error
Code
Description
Action/ Possible Failing FRU
45C00000 Memory check-stop.
(Uncorrectable
memory error)
One of the memory cards, one of the memory DIMMs, or the system planar is
failing. If the cluster bay comes ready, display and repair the related problem log.
Connect the service terminal to the working cluster bay and use the Repair
Menu Show / Repair Problems Needing Repair option.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
If the cluster bay hangs, go to
″
MAP 4540: Cluster Minimum Configuration
″
in
chapter 3 of the Enterprise Storage Server Service Guide, Volume 1
48800909 System VPD error.
1. Check the cable to the cluster operator panel.
2. Replace cluster operator panel. Remember to move EEPROM from old panel
to new panel, unless the EEPROM itself is bad.
3. Replace the I/O Planar.
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
4880090A Generic VPD error.
If the cluster bay hangs, go to
″
MAP 4540: Cluster Minimum Configuration
″
in
chapter 3 of the Enterprise Storage Server Service Guide, Volume 1.
4880090B Error identifying
system type using
VPD.
The VPD is read through the I2C bus on the following FRUs:
v
Cluster Operator Panel
v
I/O planar
v
Service Processor Card (model E10/E20 only; the model F10/F20 service
processor is on the I/O planar).
v
System planar
v
CPU cards
v
Memory cards and DIMMs (model F10/F20 only)
Note: Go to
″
MAP 4700: Cluster Bay FRU Replacement
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
4880090C Jtag unable to confirm
system type using
system VPD.
Verify that all cards installed in the cluster bay are valid cards. If it still fails, call
the next level of support.
4B2xxx00 Check-stop
1. Use the service processor General User menu, Read Progress indicators
from the Last System Boot option to display the last posted code. If the code
is
″
E105
″
or
″
0xxx
″
, continue at the next step. If the code is not
″
E105
″
or
″
0xxx
″
, look up the code and action in “Chapter 9: Error Messages,
Diagnostic Codes, and Service Reports” on page 71.
2. Remove the CPU card in P1–C2 (farthest away from the memory cards). If
the problem is resolved, replace the removed CPU card. If not, continue.
3. Exchange the CPU card in P1–C1 (closest to the memory cards) with the
CPU card removed in step one. If the problem is resolved, replace the
removed CPU card. If not, continue.
4. Return both CPU cards to their original slots.
5. Go to
″
MAP 4540: Cluster Minimum Configuration
″
in chapter 3 of the
Enterprise Storage Server Service Guide, Volume 1.
4B2xxx01 Check-stop - Slot
P1-C1 failure
1. CPU card in P1-C1 (closest to the memory cards).
2. System planar.
3. I/O planar (model F10/F20 only).
Codes
94
VOLUME 3, ESS Service Guide
Содержание E10
Страница 2: ......
Страница 68: ...52 VOLUME 3 ESS Service Guide...
Страница 192: ...2105 Exception Symptom Codes 176 VOLUME 3 ESS Service Guide...
Страница 198: ...Translation 182 VOLUME 3 ESS Service Guide...
Страница 256: ...CPI Diagnostic Progress Code Stop 240 VOLUME 3 ESS Service Guide...
Страница 257: ...CPI Diagnostic Progress Code Stop Appendix C Isolating a CPI Diagnostic Progress Code Stop 241...
Страница 258: ...CPI Diagnostic Progress Code Stop 242 VOLUME 3 ESS Service Guide...
Страница 259: ...Glossary of Terms and Abbreviations Copyright IBM Corp 1999 2000 243...
Страница 277: ......
Страница 278: ...Printed in the United States of America on recycled paper containing 10 recovered post consumer fiber SY27 7609 06...
Страница 279: ...Spine information Enterprise Storage Server VOLUME 3 ESS Service Guide...