System Description - Output Functions
Fusion4 MSC-L
Part No.: 4418309_Rev09
3- 52
Installation & Operation Manual
Honeywell
3.9 Output Functions
3.9.1 General
The following table describes the electronic output functions the MSC-L
supports.
3.9.2 Pulse Output (PO DC)
3.9.2.1 Functional Description
The Pulse Output DC (PO DC) allows the controller to switch DC
signals to interface a PLC, TAS, or other systems. The PO is not
designed to switch the high-current loads.
The two output terminals behave as “volt-free” contacts and require an
external power supply to drive a load.
Real-time PO circuitry contains a multiplexer and a selector, which is
controlled by a micro controller to select certain pulse input circuitry to
the pulse output channel.
Factored PO circuitry is controlled by a micro controller to present a
certain pulse input signal factored (scaled) to the pulse output channel.
FIGURE 3-31 illustrates the simplified block diagram of the external PO
connections.
Output function
I/O block name
CAN-ARM-MSC
CAN-IN-OUT-MSC
Pulse Output DC
PO
-
Analog Output (4-20 mA Passive)
AO
AO
Digital Output Electromechanical
Relay DC
-
DO-EMR DC
Digital Output Electromechanical
Relay AC or DC
-
DO-EMR AC or DC
Digital Output AC (Solid State
Relay)
DO-SSR
DO-SSR