Operation - Arm Configuration
Part No.: 4418309_Rev09
Fusion4 MSC-L
Honeywell
Installation & Operation Manual
5 - 209
5.15.8.1 Flow Rate
5.15.8.1.1 Initial Flow
.
Alarms
5.15.8.1.2 Full Flow
.
Alarms
Entity
Description
Value range
[
Alarm action
]
With this entity you can configure the
alarm behavior, in case this particular
alarm occurs.
<Disabled>
(default)
<Display>
<Display shutdown>
<Display pause>
[Alarm start delay]
With this entity you can configure a
delay after which the MSC-L starts
monitoring the initial flow rate alarm.
<0>
s
... <255>
s
(default =
<5>
s)
[Low percentage]
With this entity you can configure the
low percentage value for monitoring the
initial flowrate alarm. The initial flowrate
low alarm is raised if the actual flowrate
during the initial flow stage is below the
configured initial flowrate by low
percentage value.
<1.0>
%
... <99.99>
%
(default =
<5.0> %
)
[High percentage]
With this entity you can configure the
high percentage value for monitoring
the initial flowrate alarm. The initial
flowrate high alarm is raised if the
actual flowrate during the initial flow
stage is above the configured initial
flowrate by high percentage value.
<1.0>
%
... <99.99>
%
(default =
<5.0>
%)
Entity
Description
Value range
[
Alarm action
]
With this entity you can configure the
alarm behavior, in case this particular
alarm occurs.
<Disabled>
(default)
<Display >
<Display shutdown>
<Display pause>
[Alarm start delay]
With this entity you can configure a
delay after which the MSC-L starts
monitoring the full flow rate alarm, after
the load profile enters the full flow state.
<0>
s
... <255>
s
(default =
<5> s
)
[Low percentage]
With this entity you can configure the
low percentage value for monitoring full
flowrate alarm. The full flowrate low
alarm is raised if the actual flowrate
during the full flow stage is below the
configured full flowrate by low
percentage value.
<1.0>
%
... <99.99>
%
(default =
<5.0>
%)
[High percentage]
With this entity you can configure the
high percentage value for monitoring
the full flowrate alarm. The full flowrate
high alarm is raised if the actual
flowrate during the full flow stage is
above the configured full flowrate by
high percentage value.
<1.0>
%
... <99.99>
%
(default =
<5.0>
%)