Operation - Stream Configuration
Part No.: 4418309_Rev09
Fusion4 MSC-L
Honeywell
Installation & Operation Manual
5 - 183
The
Additive Stream Config. . Stream n . Leaking Valve
screen is
displayed with the following entities.
5.14.2.4.2 No Additive
On the
Additive Stream Config . Stream n . Alarms
screen, select
<No
additive>
.
The
Additive Stream Config. . Stream n . No Additive
screen is
displayed with the following entities.
5.14.2.4.3 No Pump
On the
Additive Stream Config . Stream n . Alarms
screen, select
<No
pump>
.
Entity
Description
Value range
[Alarm action]
With this entity you can configure the
alarm behavior, in case this particular
alarm occurs.
<Disabled>
<Display>
<Display shutdown>
(default)
<Display pause>
[Leaking volume limit]
With this entity you can set the
maximum amount of additive volume
measured
[Leaking timeout period]
before a leaking valve alarm is
generated.
If this limit is exceeded, an alarm
occurs depending on the
[Alarm
action]
.
<0>
ml
... <999>
ml
(default =
<100.00>
ml)
[Leaking timeout period]
With this entity you can set the time in
seconds in which the
[Leaking volume
limit]
is checked.
<1>
s
... <99>
s
(default =
<60>
s)
Entity
Description
Value range
[Alarm action]
With this entity you can configure the
alarm behavior, in case this particular
alarm occurs.
<Disabled>
(default)
<Display>
<Display shutdown>
<Display pause>
[No additive timeout]
With this entity you can set the time in
seconds in which additive stream
pulses should be received when the
solenoid is opened. The additive
stream pulses are not received after
the configured
[number of retries]
and
an alarm occurs depending on the
[Alarm action]
.
<1>
s
... <9>
s
(default =
<2>
s)