Operation - Stream Configuration
Part No.: 4418309_Rev09
Fusion4 MSC-L
Honeywell
Installation & Operation Manual
5 - 167
5.14.1.5.0.5 Block Valve
On the
Stream Config . Stream n . Alarms
screen, select
<Block valve>
.
The
Stream Config . Stream n . Block valve
screen
appears.
5.14.1.5.0.5.1 Block Valve fault
On the
Stream Config . Stream n . Block valve
screen, select
<Block
valve fault>
.
The
Stream Config. . Stream n . Block Valve fault
screen is displayed
with the following entities.
[Pump feedback timeout]
With this entity you can set the time in
seconds in which the product stream
hydraulic pump must give feedback to
the MSC-L. If no hydraulic pump
feedback is received in
[Pump
feedback timeout]
, an alarm occurs
depending on the
[Alarm action]
.
<1> s ... <255> s
(default =
<15> s
)
Entity
Description
Value range
[Alarm action]
With this entity you can configure the
alarm behavior, in case this particular
alarm occurs.
<Disabled>
<Display>
<Display shutdown>
<Display pause>
[Feedback timeout]
With this entity you can set the time in
seconds in which the product stream
block valve must give feedback to the
MSCL. If no feedback is received in
[feedback timeout]
an alarm occurs
depending on
[Alarm action]
.
<1> s ... <255> s
(default =
<15> s
)
Entity
Description
Value range