Operation - Stream Configuration
Fusion4 MSC-L
Part No.: 4418309_Rev09
5 - 184
Installation & Operation Manual
Honeywell
The
Additive Stream Config. . Stream n . No Pump
screen is
displayed with the following entities.
5.14.2.4.4 Block Valve Fault
On the
Additive Stream Config . Stream n . Alarms
screen, select
<Block valve fault>
.
The
Additive Stream Config. . Stream n . Block Valve Fault
screen is
displayed with the following entities.
5.14.2.4.5 Deviation
On the
Additive Stream Config . Stream n . Alarms
screen, select
<Deviation>
.
The
Additive Stream Config. . Stream n . Deviation
screen is
displayed with the following entities.
Entity
Description
Value range
[Alarm action]
With this entity you can configure the
alarm behavior, in case this particular
alarm occurs.
<Disabled>
(default)
<Display>
<Display shutdown>
<Display pause>
[Pump feedback timeout]
With this entity you can set the time in
seconds in which the additive pump
must provide a feedback to the MSC. If
the feedback from the pump is not
received in
[Pump feedback timeout],
then an alarm occurs depending on the
[Alarm action]
.
<1>
s
... <255>
s
(default =
<15>
s)
Entity
Description
Value range
[Alarm action]
With this entity you can configure the
alarm behavior, in case this particular
alarm occurs.
<Disabled>
(default)
<Display>
<Display shutdown>
<Display pause>
[Feedback timeout]
With this entity you can set the time in
seconds in which the additive pump
must providea feedback to the MSC. If
the feedback from the pump is not
received in
[Feedback timeout]
, then an
alarm occurs depending on the
[Alarm
action]
.
<1>
s
... <255>
s
(default =
<15>
s)
Entity
Description
Value range
[Alarm action]
With this entity you can configure the
alarm behavior, in case this particular
alarm occurs.
<Disabled>
<Display>
(default)
<Display shutdown>
<Display pause>