Operation - Calibration
Fusion4 MSC-L
Part No.: 4418309_Rev09
5 - 268
Installation & Operation Manual
Honeywell
place (for example, to observe the result) until the process
continues.
7. Enter the start delay in seconds and then select
<Confirm>
.
The
Calibration . Arm n . Stream n. Wizard
screen appears with
the Preset volume, Flowrate, Start delay time in seconds, and
the Metered Volume.
8. Select
<OK>
on the IR controller or LAD to start the calibration.
The countdown of the delay time starts. After the expiration of
the delay time, the calibration process starts.