Alarm Handling - List of all alarms
Fusion4 MSC-L
Part No.: 4418309_Rev09
6 - 18
Installation & Operation Manual
Honeywell
NOTE: * Please note that the corresponding parameters
need to be configured on External additive controller.
The parameter names used here are specific to
MSC-A but similar parameters will be available on
other devices.
6.8.7 Dual Bay Alarms
Pulse Hardware [*]
This alarm is generated when the pulse input module
detects the following error conditions.
• Not able to read the information from the PIC controller.
• Pulse overflow errors.
• BAD health of the pulse input function.
Or
• The dual pulse input are out of phase (only if configured
for quad pulse).
Tank Empty [*]
This alarm is generated when a Tank empty signal is
received. This signal is received only when the I/O Binding
input (DI, PI, and so on) are not active for the Tank empty
input.
Ext. add. Device Firm
-
ware failure [*]
General fail alarm/ any other alarm not listed here.
Ext. add. Device
Program failure [*]
This alarm is generated when external additive detects HMI
error, Arm board missing, batch permissive failure or stream
start failure.
Power Failure [*]
External additive controller sees a power failure.
License Error [*]
Incorrect license on external additive controller.
Service due reminder
[*]
This alarm is generated when the
[Next schedule service]
date expires.
Alarm
Cause
Swing arm invalid
position
Both [Bay 1 in position] and [Bay 2 in position] read an
active signal.
Swing arm invalid
transition
The arm changes its position while the arm is not idle. This
alarm is not configurable and always terminates the batch.
Alarm
Cause