Introduction
Append
ix
B
B–4
Serial Network
Parameter
Settings
Several parameter settings are necessary to configure serial communications, listed below.
For inverters on the same network, some settings must match from inverter to inverter. These
include:
• Baud rate
• Data bits
• Parity
• Stop bits
However, the node address on each inverter must be unique, used only once on the network.
Function
Code
Item
Value
Description
C070
Data command source
02
Digital operator
03
RS485 connector
04
Expansion card #1
05
Expansion card #2
C071
Baud rate
02
Loop-back test
03
2400 bps
04
4800 bps
05
9600 bps
06
19200 bps
C072
Node address
1 to 32,
FF
1 to 32 – Node or station address (unique
to each inverter or device)
FF – Automatic broadcast (to all nodes on
transmit, allowed only on certain
commands (refer to each command
description in this appendix)
C073
Data bits
07
7 bits
08
8 bits
C074
Parity
00
none
01
Even parity
02
Odd parity
C075
Stop bits
01
1 bit
02
2 bits
C078
Wait time
0 to 1000
0 to 1000 ms time that the inverter waits
to respond to network master
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......