“F” Group: Main Profile Parameters
Configur
ing Dr
iv
e
P
a
ra
meters
3–8
“F” Group: Main Profile Parameters
The basic frequency (speed) profile is
defined by parameters contained in the
“F” Group as shown to the right. The
output frequency is set in Hz, but accel-
eration and deceleration are specified
seconds (the time to ramp from zero to
maximum frequency, or from maximum
frequency to zero). The motor direction
parameter determines whether the
keypad Run key produces a FW or RV
command. This parameter does not
affect the [FW] terminal or [RV] intelligent terminal function, which you configure separately.
Acceleration 1 and Deceleration 1 are the standard default accel and decel values for the main
profile. Accel and decel values for an alternative profile are specified by using parameters Ax92
through Ax93. The motor direction selection (F004) determines the direction of rotation as
commanded only from the keypad. This setting applies to any motor profile (1st, 2nd, or 3rd) in
use at a particular time.
Output
frequency
F001
F002
F003
t
“F” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(EU)
–FU
(US)
–FR
(JP)
F001
Output frequency
setting
Standard default target
frequency that determines
constant motor speed
Range is 0 to 400 Hz
✔ ✔
0.00
0.00
0.00
Hz
>F001 SET-Freq.
TM 0000.00Hz
2FS 0000.00Hz
3FS 0000.00Hz
TM 0000.00Hz
JG 0000.00Hz
1S 0000.00Hz
15S 0000.00Hz
OP1 0000.00Hz
OP2 0000.00Hz
RS485 0000.00Hz
F002
Acceleration (1) time
setting
Standard default accelera-
tion
Range is 0.01 to 3600 sec.
✔ ✔
30.0
30.0
30.0
sec.
>F002 ACCEL
TIME1 0030.00s
F202
Acceleration (1) time
setting, 2nd motor
Standard default accelera-
tion, 2nd motor
Range is 0.01 to 3600 sec.
✔ ✔
30.0
30.0
30.0
sec.
>F202 2ACCEL
TIME1 0030.00s
F302
Acceleration (1) time
setting, 3rd motor
Standard default accelera-
tion, 3rd motor
Range is 0.01 to 3600 sec.
✔ ✔
30.0
30.0
30.0
sec.
>F302 3ACCEL
TIME1 0030.00s
F003
Deceleration (1) time
setting
Standard default decelera-
tion
Range is 0.01 to 3600 sec.
✔ ✔
30.0
30.0
30.0
sec.
>F003 DECEL
TIME1 0030.00s
F203
Deceleration (1) time
setting, 2nd motor
Standard default decelera-
tion, 2nd motor
Range is 0.01 to 3600 sec.
✔ ✔
30.0
30.0
30.0
sec.
>F203 2DECEL
TIME1 0030.00s
F303
Deceleration (1) time
setting, 3rd motor
Standard default decelera-
tion, 3rd motor
Range is 0.01 to 3600 sec.
✔ ✔
30.0
30.0
30.0
sec.
>F303 3DECEL
TIME1 0030.00s
F004
Keypad Run key routing Two options; select codes:
00 Forward
01 Reverse
✘ ✘
00
00
00
—
>F004 DIG-RUN
SELECT FW
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......