SJ300 Inverter
Configur
ing Dr
iv
e
P
a
ra
met
e
rs
3–31
The torque developed in a motor is directly proportional to the current in the windings, which is
also proportional to the heat generated (and temperature, over time). Therefore, you must set
the thermal overload threshold in terms of current (amperes) with parameter B012. The range is
50% to 120% of the rated current for each inverter model. If the current exceeds the level you
specify, the inverter will trip and log an event (error E5) in the history table. The inverter turns
the motor output OFF when tripped. Separate settings are available for the second and third
motors (if applicable), as shown in the table below.
For example, suppose you have inverter model
SJ300-110LFE. The rated motor current is 46A.
The setting range is (0.2 * 46) to (1.2 *46), or
9.2A to 55.2A. For a setting of B012 = 46A
(current at 100%), the figure to the right shows
the curve.
The electronic thermal characteristic adjusts the
way the inverter calculates thermal heating,
based on the type of load connected to the motor,
as set by parameter B013.
CAUTION:
When the motor runs at lower
speeds, the cooling effect of the motor’s internal
fan decreases.
The table below shows the torque profile settings. Use the one that matches your load.
Reduced Torque Characteristic
– The example below shows the effect of the reduced torque
characteristic curve (for example motor and current rating). At 20Hz, the output current is
reduced by a factor of 0.8 for given trip times.
Function
Code
Function/Description
Data or Range
B012 / B212
/ B312
Electronic thermal setting (calculated
within the inverter from current output)
Range is 0.2 * rated current to
1.2 * rated current
Function Code
Data
Function/Description
B013 / B213 / B313
00
Reduced torque
01
Constant torque
02
Free-setting
Trip
time (s)
Trip current at 60 Hz
60
0.5
0
53.4
69
92
A
116% 150%
200%
Trip
time (s)
Reduced trip current at 20 Hz
Trip current
reduction
factor
x 1.0
x 0.8
x 0.6
0
5
20
60
Hz
A
60
0.5
0
73.6
42.7 55.2
92.8% 120%
160%
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......