Monitoring Trip Events, History, & Conditions
T
roub
leshooting
and Maintenance
6–8
Trip History and
Inverter Status
We recommend that you first find the cause of the fault before attempting clearing it. When a
fault occurs, the inverter stores important performance data at the moment of the fault. To
access the data, use the monitor functions (Dxxx) and select D081 for details about the present
fault (E
n
). The previous five faults are stored in D081 to D086, with D (E
n-1
to E
n-5
). Each error
shifts D081–D085 to D082–D086, and writes the new error to D081.
The following Monitor Menu map shows how to access the error codes. When fault(s) exist,
you can review their details by first selecting the proper function: D081 is most recent, and
D086 is the oldest.
1
Error Code
Error
exists?
Output frequency at
trip point
Motor current at
trip point
DC bus voltage at
trip point
No error
Yes
No
2
1
2
2
E 0 7.2
6 0.00
4.0 0
2 7 0.0
1 5
1 8
d
0 8 1
d
0 8 6
d
0 8 2
1
1
1
1
1
Cumulative inverter
operation time
at trip point
Cumulative power-
ON time at trip point
1
2
Current Trip
Conditions
Trip History
Monitor Menu
FUNC.
FUNC.
FUNC.
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......