SJ300 Inverter
Configur
ing Dr
iv
e
P
a
ra
met
e
rs
3–19
Derating of DC Braking
– The inverter uses an internal carrier frequency (set by A059) to
generate a DC braking voltage (do not confuse with main inverter output carrier frequency set
by B083). The maximum DC braking force available to the inverter is more limited with higher
DC braking carrier frequency settings for A059 according to the graphs below.
“A” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(EU)
–FU
(US)
–FR
(JP)
A051 DC braking enable
Two options; select codes:
00 Disable
01 Enable
✘ ✔
00
00
00
—
>A051 DCB
Mode OFF
A052 DC braking frequency
setting
The frequency at which DC
braking activates during
decel.
Range is 0.00 to 60.00 Hz
✘ ✔
0.50
0.50
0.50
Hz
>A052 DCB
F 00.50Hz
A053 DC braking wait time
The delay after reaching the
DC braking frequency, or
[DB] signal, before DC
braking begins.
Range is 0.0 to 5.0 seconds
✘ ✔
0.0
0.0
0.0
sec.
>A053 DCB
WAIT 0.0s
A054 DC braking force during
deceleration
Variable DC braking force.
Range is from 0% to 100%
✘ ✔
0.
0.
0.
%
>A054 DCB
STP-V 000%
A055 DC braking time for
deceleration
Sets the duration for DC
braking during decel. Range
is 0.0 to 60.0 seconds
✘ ✔
0.0
0.0
0.0
sec.
>A055 DCB
STP-T 00.0s
A056 DC braking / edge or
level detection for [DB]
input
Two options; select codes:
00 Edge detection
01 Level detection
✘ ✔
01
01
01
—
>A056 DCB
KIND LEVEL
A057 DC braking force for
starting
Variable DC braking force.
Range is 0 to 100%
✘ ✔
0.
0.
0.
%
>A057 DCB
STA-V 000%
A058 DC braking time for
starting
Sets the duration for DC
braking before accel.
Range is 0.0 to 60.0 seconds
✘ ✔
0.0
0.0
0.0
sec.
>A058 DCB
STA-T 00.0s
A059 DC braking carrier
frequency setting
Range is 0.5 to 15 kHZ for
models up to –550xxx,
range is 0.5 to 10kHz for
750xxx to 1500xxx models
✘ ✘
3.0
3.0
3.0
kHz
>A059 DCB
CARRIER 05.0kHz
Max.braking
ratio (%)
10
20
30
40
50
60
70
3
5
7
9
11
13
DC braking carrier frequency
10
20
30
40
50
60
70
3
5
7
9
(10)
(22)
(34)
(46)
Max.braking
ratio (%)
DC braking carrier frequency
(10)
(20)
(40)
Models 75 – 132kW
Models 11 – 55kW
80
90
100
80
90
100
15
(75)
kHz
10
(60)
kHz
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......