Using Intelligent Input Terminals
Oper
ations
a
nd Moni
tor
ing
4–24
In the previous timing diagram, when the motor has been started across the line, Mg2 is
switched OFF and Mg3 is switched ON. With the Forward command to the inverter already
ON, the [CS] terminal is switched ON and relay Mg1 contacts close. The inverter will then read
the motor RPM (frequency matching). When the [CS] terminal is switched OFF, the inverter
applies the
Retry wait time before motor restar
t parameter (B003).
Once the delay time has elapsed the inverter will then start and match the frequency (if greater
than the threshold set by B007). If the ground fault interrupter breaker (GFI) trips on a ground
fault, the bypass circuit will not operate the motor. When an inverter backup is required, take
the supply from the bypass circuit GFI. Use control relays for [FW], [RV], and [CS].
The commercial power source switching function requires you to assign [CS] to an intelligent
input terminal, using option code 14.
Opt.
Code
Symbol
Function Name
Input
State
Description
14
CS
Commercial Power
Change
ON
OFF-to-ON transition signals the inverter
that the motor is already running at
powerup (via bypass), thus suppressing
the inverter’s motor output in Run Mode
OFF
ON-to-OFF transition signals the inverter
to apply a time delay (B003), frequency
match its output to existing motor speed,
and resume normal Run Mode operation
Valid for inputs:
C001, C002, C003, C004,
C005, C006, C007, C008
Required
settings:
B003, B007
Notes:
•
If an over-current trip occurs during frequency
matching, extend the retry wait time B003.
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
See I/O specs on page
.
Example: (Requires input configuration—
see page
. Jumper position shown is
for –xFU/-xFR models; for –xFE models,
see page
CS
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......