SJ300 Inverter
Configur
ing Dr
iv
e
P
a
ra
met
e
rs
3–61
Miscellaneous
Functions
The following table contains miscellaneous functions not in other function groups.
C102/C103: Reset Mode / Restart Mode –
The reset mode selection, set via parameter C102,
determines how the inverter responds to the [RS] intelligent input signal or keypad Stop/Reset
key in a trip condition. The options allow you to cancel the trip on either the OFF-to-ON or
ON-to-OFF transition of [RS], and if desired, stop the inverter if it is in Run Mode. A trip event
causes the inverter output to the motor to turn OFF immediately. If in Run Mode when the trip
occurred, the inverter and motor will enter free-run stop (coasting) operation. In some applica-
tions, the motor and load will still be coasting when the inverter returns to normal Run Mode
operation. For that situation, you can configure the inverter output (C103=00) to resume opera-
tion from 0 Hz and accelerate normally. Or, you can configure the inverter (C103=01) to
resume operation from the current speed of the motor (
frequency matching
)—often used in
applications such as HVAC.
“C” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(EU)
–FU
(US)
–FR
(JP)
C091
Debug mode enable
Two option codes:
00 No display
01 Display
✘ ✔
00
00
00
—
>C091 INITIAL
DEBG OFF
C101
Up/Down memory
mode selection
Controls speed setpoint for
the inverter after power
cycle. Two option codes:
00 Clear last frequency
(return to default
frequency F001)
01 Keep last frequency
adjusted by UP/DWN
✘ ✔
00
00
00
—
>C101 UP/DWN
DATA NO-STR
“C” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(EU)
–FU
(US)
–FR
(JP)
C102
Reset mode selection
Determines response to
Reset input [RST].
Three option codes:
00 Cancel trip state at input
signal ON transition,
Stops inverter if in Run
Mode
01 Cancel trip state at signal
OFF transition, Stops
inverter if in Run Mode
02 Cancel trip state at input
signal ON transition, no
effect if in Run Mode.
✔ ✔
00
00
00
—
>C102 RESET
SELECT ON
C103
Restart mode after reset
Two option codes:
00 Restart at 0 Hz
01 Resume operation after
frequency matching
✘ ✔
00
00
00
—
>C103 RESET
f-Mode ZST
C111
Overload setting (2)
Range is 0.00 times rated
current to 2.00 times rated
current
✘ ✔
Rated current for
each inverter model
A
>C111 OL
LEVEL2 0016.5A
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......