SJ300 Inverter
Oper
ati
ons
and Monitor
ing
4–37
Torque Limit
The Torque Limit function limits the motor output torque for sensorless vector control, sensor-
less vector control 0Hz domain, or vector control with feedback.
In the torque limit function, the following operational modes are available (selected by B040):
1.
Four-quadrant individual setting mode – This mode sets torque limit in 4 zones, forward
driving and regenerating, reverse driving and regenerating. Limits for each quadrant are set
with B041 – B044 individually.
2.
Terminal selection mode – By use of torque limit select intelligent input terminals 1 and 2,
this mode changes and uses torque limits 1 – 4 set in B041 – B044. Selected torque limit
range is valid in all four quadrants.
3.
Analog input mode – This mode sets torque limit value by the voltage applied to terminal
[O2] (referenced to [L] for ground. An input of 0 – 10V corresponds to the torque limit
value of 0 to 200%. The selected torque limit value is valid in all four quadrants (whether
forward or reverse move, driving or regenerating).
4.
Expansion Cards 1 and 2 – This function is valid when using the expansion card (SJ-DG).
Please refer to the SJ-DG instruction manual.
When the torque limit enable function [TL] is assigned to an intelligent input terminal, torque
limiting occurs only when [TL] is ON. When the [TL] input is OFF, the inverter always uses the
default torque control limit of 200% maximum. That torque limit value corresponds to 200% of
the maximum inverter output current. Therefore, the output torque also depends on the particu-
lar motor in use. When the over-torque output [OTQ] is assigned in the intelligent output selec-
tion, it turns ON when the inverter is performing torque limiting.
Note 1:
Unavailable for A344
Note 2:
Unavailable for A244 and A344
Code
Function
Data or Range
Description
A044 /
A244
Control method
selection
00
01
02
03
04
05
V/f Constant torque
V/f Variable torque
V/f Free-setting torque *1
Sensorless vector *1
Sensorless vector, 0 Hz domain *1
Vector control with sensor *2
B040
Torque limit
selection
00
01
02
03
04
4-quadrant individual setting
Terminal selection
Analog [O2] input
Expansion card 1
Expansion card 2
B041
Torque limit 1
0 to 200%
Forward-driving in 4-quadrant mode
B042
Torque limit 2
0 to 200%
Reverse-regenerating in 4-quadrant
mode
B043
Torque limit 3
0 to 200%
Reverse-driving in 4-quadrant mode
B044
Torque limit 4
0 to 200%
Forward-regenerating in 4-quadrant
mode
C001
to
C008
Intelligent input
terminal [1] to [8]
function
40
41
42
Torque limit enable
Torque limit selection, bit 1 (LSB)
Torque limit selection, bit 2 (MSB)
C021
to
C025
Intelligent output
terminal [11] to [15]
function
10
In torque limit
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......