Determining Wire
and Fuse Sizes
This section includes tables for 200V class and 400V class inverters (on the next page). The
following notes will help you read the tables in this section:
• Locate the row corresponding to the motor size and particular inverter in your application.
The maximum motor current determines the recommended wire sizes.
• The length column specifies that some inverters can optionally use a smaller wire gauge if
the wires are shorter than 10m and the inverter is located in an enclosure.
• Power Lines columns include wires connecting to terminals [R, S, T, U, V, W, P, PD, and N].
Only power input and motor leads will be fused: [R, S, T, U, V, and W]. The breaker ratings
(GFI—ground fault interrupter) are slightly higher than fuse ratings to allow for nominal
surges without tripping.
• The chassis ground columns list the Hitachi-recommended AWG and the minimal AWG for
UL conformity.
• The optional external braking resistor wiring only applies to a few models that have a built-
in braking unit. The other models use an optional external braking unit.
• Parallel wires increase effective wire gauge, and are denoted by “||” in the tables.
• Signal Lines, not listed in these tables, connect to the removable logic connector. The recom-
mended wire gauge for all wiring to the logic connector is 28 AWG (0.75 mm
2
). Be sure to
use shielded wire for any analog signals.
* See notes for wiring tables on the following page.
Motor
Output
200V
Inverter
Models
Wiring *1
Power Lines *3
Chassis Ground
Brake Res.
HP
kW
AWG
mm
2
Fuse
(UL-
rated,
class J,
600V)
Breaker
(GFI
type) *2
AWG,
rec.
AWG,
UL
mm
2
AWG
mm
2
1/2
0.4
SJ300–004LFU
20
1.25
10A
10A
16
14
1.25
20
1.25
1
0.75
SJ300–007LFU
18
1.25
10A
10A
16
14
1.25
18
1.25
2
1.5
SJ300–015LFU
14
2
10A
10A
16
14
1.25
14
2
3
2.2
SJ300–022LFU
14
2
15A
15A
16
14
1.25
14
2
5
3.7
SJ300–037LFU
10
3.5
20A
20A
10
12
3.5
10
3.5
7.5
5.5
SJ300–055LFU
8
5.5
30A
30A
8
10
5.5
8
5.5
10
7.5
SJ300–075LFU
6
8
40A
40A
8
10
8
8
5.5
15
11
SJ300–110LFU
4
14
60A
60A
4
10
14
8
5.5
20
15
SJ300–150LFU
2
22
80A
80A
3
8
22
—
—
25
18.5
SJ300–185LFU
1
14 || 14
100A
100A
3
8
22
—
—
30
22
SJ300–220LFU
1/0
14 || 14
125A
125A
2
8
30
—
—
40
30
SJ300–300LFU
1/0 || 1/0
22 || 22
150A
150A
2
6
30
—
—
50
37
SJ300–370LFU
1/0 || 1/0
30 || 30
175A
175A
1/0
6
38
—
—
60
45
SJ300–450LFU
1/0 || 1/0
38 || 38
225A
225A
3/0
6
38
—
—
75
55
SJ300–550LFU
2/0 || 2/0
60 || 60
250A
250A
3/0
4
60
—
—
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......