SJ300 Inverter
Oper
ati
ons
and Monitor
ing
4–33
Remote Control
Up and Down
Functions
The [UP] [DWN] terminal functions can adjust the output frequency for remote control while
the motor is running. The acceleration time and deceleration time used with this function is the
same as for normal operation ACC1 and DEC1 (2ACC1,2DEC1). The input terminals operate
as follows:
• Acceleration - When the [UP] contact is turned ON, the output frequency accelerates from
the current value. When it is turned OFF, the output frequency maintains its current value.
• Deceleration - When the [DWN] contact is turned ON, the output frequency decelerates
from the current value. When it is turned OFF, the output frequency maintains its current
value.
In the graph below, the [UP] and [DWN] terminals activate while the Run command remains
ON. The output frequency responds to the [UP] and [DWN] commands.
It is possible for the inverter to retain the frequency set from the [UP] and [DWN] terminals
through a power loss. Parameter C101 enables/disables the memory. If disabled, the inverter
retains the last frequency before an UP/DWN adjustment. Use the [UDC] terminal to clear the
memory and return to the original set output frequency.
Opt.
Code
Symbol
Function Name
Input
State
Description
27
UP
Remote Control
UP Function
ON
Accelerates (increases output frequency)
motor from current frequency
OFF
Output to motor operates normally
28
DWN
Remote Control
DOWN Function
ON
Decelerates (decreases output frequency)
motor from current frequency
OFF
Output to motor operates normally
29
UDC
Remote Control
Data Clear
ON
Clears the Up/down frequency memory
OFF
No effect on Up/down memory
Valid for inputs:
C001, C002, C003, C004,
C005, C006, C007, C008
Required
settings:
A001 = 02
C101 = 01 (enables memory)
Notes:
•
This feature is available only when the
frequency command source is programmed
for operator control. Confirm A001 is set to
02.
•
This function is not available when [JG] is in
use.
•
The range of output frequency is 0 Hz to the
value in A004 (maximum frequency setting).
•
The Remote Control Up/Down function
varies the inverter speed by directly writing to
the F001 output frequency setting.
Output
frequency
[UP]
[FW, RV]
[DWN]
t
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
See I/O specs on page
.
Example: (Requires input configuration—
see page
. Jumper position shown is
for –xFU/-xFR models; for –xFE models,
see page
.)
UDC DWN
UP
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......