Analog Output Operation
Oper
ations
a
nd Moni
tor
ing
4–62
Analog Output Operation
In the system design for inverter applications it is sometimes useful to monitor inverter opera-
tion from a remote location. In some cases, this requires only a panel-mounted analog meter
(moving-coil type). In other cases, a controller device such as a PLC may monitor and
command the inverter frequency and other functions. The inverter can transmit the (real-time)
output frequency, current, torque, or other parameters to the controller to confirm actual opera-
tion. The monitor output terminal [FM] serves these purposes.
[FM] Terminal
The inverter provides an analog/digital output on
terminal [FM] (frequency monitor). It uses
terminal [CM1] as digital GND reference. While
many applications use this terminal to monitor
the output frequency, you can configure terminal
[FM] to transmit one of several parameters.
Most use
pulse-width modulation
(PWM) to
represent the value, while one parameter uses
frequency modulation
(FM) to represent the
value. Do not confuse the notation for terminal
[FM] (with brackets) with FM signal type.
The following table lists the configurations for terminal [FM]. Use function C027 to configure.
Note 1:
Display substitutes only during sensorless vector control, 0Hz domain sensorless
vector control, and vector control
PWM Signal Type
The
pulse-width modulated
signal at terminal
[FM] is primarily designed for driving a moving-
coil meter. The pulse-width modulated signal is
automatically averaged by the inertia of the
moving-coil mechanism—converting the PWM
signal to an analog representation. Be sure to use
a 10V full-scale DC voltmeter.
The signal characteristics of terminal [FM] in
PWM signal configuration is shown below
Func.
Code
Description
Waveform
Full Scale Value
C027
00
Output frequency
PWM
0 – Max. frequency (Hz)
01
Output current
PWM
0 – 200%
02
Output torque *1
PWM
0 – 200%
03
Output frequency
FM
0 – Max. frequency (Hz)
04
Output voltage
PWM
0 – 100%
05
Input electric power
PWM
0 – 200%
06
Thermal load ratio
PWM
0 – 100%
07
LAD frequency
PWM
0 – Max. frequency (Hz)
D GND
Analog/digital Output
See I/O specs on page
H O2
FM
AM
O
OI
L
FW
TH
PLC
P24
CM1
AMI
H O2
FM
AM
O
OI
L
FW
TH
PLC
P24
CM1
AMI
+
–
0 to 10V,
1 mA
[FM]
[FM] output value
t
T
---
=
Period T = 6.4ms constant (156 Hz)
Selects FM type output
= [FM] terminal 8-bit gain setting
B081
C27=00, 01, 02, 04, 05, 06, 07
t
10V
0V
t
T
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......