Using Intelligent Output Terminals
Oper
ations
a
nd Moni
tor
ing
4–44
Frequency Arrival
Signals
The
Frequency Arrival
group of outputs help coordinate external systems with the current
velocity profile of the inverter. As the name implies, output [FA1] turns ON when the output
frequency arrives
at the standard set frequency (parameter F001). Outputs [FA2] through [FA5]
provide variations on this function for increased flexibility, relying on two programmable accel/
decel thresholds. For example, you can have an output turn ON at one frequency during accel-
eration, and have it turn OFF at a different frequency during deceleration. All transitions have
hysteresis to avoid output chatter if the output frequency is near one of the thresholds.
Opt.
Code
Symbol
Function Name
Output
State
Description
01
FA1
Frequency arrival
type 1 – constant
speed
ON
when output to motor is at the standard set
frequency F001
OFF
when output to motor is not at the set
frequency F001
02
FA2
Frequency arrival
type 2 – over-
frequency
ON
when output to motor is at or above the FA
threshold 1(C042) during accel
OFF
when the output to motor is below the FA
threshold 1 (C043) during decel
06
FA3
Frequency arrival
type 3 – at
frequency
ON
when output to motor is at the FA thresh-
old 1 (C042) during accel, or at C043
during decel
OFF
when the output to motor is not at either
the FA threshold 1 (C042) during accel or
at C43 during decel
24
FA4
Frequency arrival
type 4 – over-
frequency (2)
ON
when output to motor is at or above the FA
threshold 2 (C045) during accel
OFF
when the output to motor is below the FA
threshold 2 (C046) during decel
25
FA5
Frequency arrival
type 5 –
at frequency (2)
ON
when output to motor is at the FA thresh-
old 2 (C045) during accel, or at C046
during decel
OFF
when the output to motor is not at either
the FA threshold 2 (C045) during accel or
at C046 during decel
Valid for
outputs:
11, 12, 13, 14, 15,
AL0 – AL2
Required
settings:
F001, for FA1
C042 & C043, for FA2 & FA3
C045 & C046, for FA4 & FA5
Notes:
•
For most applications you will need to use
only one or two of the frequency arrival type
outputs (see example). However, it is possible
assign all five output terminals to output
functions [FA1] through [FA5].
•
For each frequency arrival threshold, the
output anticipates the threshold (turns ON
early) by an amount equal to 1% of the
maximum frequency set for the inverter.
•
The output turns OFF as the output frequency
moves away from the threshold, delayed by
an amount equal to 2% of the max. frequency.
+
–
RY
See I/O specs on page
.
Inverter output
terminal circuit
CM2
13
14
15
11
12
Example: (Default output configuration
shown—see page
.)
FA1
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......