SJ300 Inverter
Oper
ati
ons
and Monitor
ing
4–15
The Bit Operation method of speed control uses up to seven intelligent inputs to select from up
to eight speeds. Since the all-switches-OFF combination selects the first speed, you only need
N-1 switches to select N speeds. With Bit Operation speed control, only one input is normally
active at a time. If multiple switches are ON, the lower numbered input takes precedence
(determines the speed). The table and figure below show how the input combinations work.
The following table lists the option codes for assigning [SF1 to [SF7] to the intelligent inputs.
0th
SF1
SF2
SF3
3rd
4th
2nd
5th
1st
7th
6th
Speed
Switches
Fwd Run
SF4
SF5
SF6
SF7
Multi-
speed
Input Function
SF7
SF6
SF5
SF4
SF3
SF2
SF1
Speed 0
0
0
0
0
0
0
0
Speed 1
—
—
—
—
—
—
1
Speed 2
—
—
—
—
—
1
0
Speed 3
—
—
—
—
1
0
0
Speed 4
—
—
—
1
0
0
0
Speed 5
—
—
1
0
0
0
0
Speed 6
—
1
0
0
0
0
0
Speed 7
1
0
0
0
0
0
0
Opt.
Code
Symbol
Function Name
Description
32
SF1
Bit-level speed select 1
Bit-level speed select, Bit 0
33
SF2
Bit-level speed select 2
Bit-level speed select, Bit 1
34
SF3
Bit-level speed select 3
Bit-level speed select, Bit 2
35
SF4
Bit-level speed select 4
Bit-level speed select, Bit 3
36
SF5
Bit-level speed select 5
Bit-level speed select, Bit 4
37
SF6
Bit-level speed select 6
Bit-level speed select, Bit 5
38
SF7
Bit-level speed select 7
Bit-level speed select, Bit 6
Valid for
inputs:
C001, C002, C003, C004,
C005, C006, C007, C008
Required
settings:
F001, A020 to A035
A019=01
Notes:
•
When all [SFx] inputs are OFF, the speed is
set by default to the value in F001.
•
When a multi-speed setting more than
50Hz(60Hz) is to be set, it is necessary to
program the maximum frequency A004 high
enough to allow that speed.
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
Example: (Requires input configuration—
see page
. Jumper position shown is
for –xFU/-xFR models; for –xFE models,
see page
SF1
SF3
SF5
SF7
SF2
SF4
SF6
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......