Using Intelligent Input Terminals
Oper
ations
a
nd Moni
tor
ing
4–12
Wiring Diagram
Conventions
The input wiring diagrams in this chapter are examples only. Default and non-default input
terminal assignments are noted throughout; your particular assignments may be different. The
wiring diagrams show the –xFU/–xFR model default [P24]–[PLC] jumper position (U.S./Jpn
versions), as shown below on the left. The common (return) for inputs is [CM1] in this case.
The diagram on the right shows the default jumper position and example input wiring for –xFE
models (Europe version). For this case, the common (return) for inputs is [P24].
Be sure the
jumper position and return terminal used match your application wiring needs.
Forward Run/
Stop and Reverse
Run/Stop
Commands
When you input the Run command via the dedicated terminal [FW], the inverter executes the
Forward Run command (high) or Stop command (low). When you input the Run command via
the programmable terminal [RV], the inverter executes the Reverse Run command (high) or
Stop command (low).
NOTE:
The parameter F004, Keypad Run Key Routing, determines whether the single Run
key issues a Run FWD command or Run REV command. However, it has no effect on the [FW]
and [RV] input terminal operation.
WARNING:
If the power is turned ON and the Run command is already active, the motor
starts rotation and is dangerous! Before turning power ON, confirm that the external Run
command is not active.
5
3
1
4
2
FW
TH
PLC
P24
CM1
5
3
1
4
2
FW
TH
PLC
P24
CM1
Default jumper
position [P24]–[PLC]
and wiring example
(used throughout this
chapter)
–xFU/–xFR models (U.S./Jpn versions):
–xFE models (Europe version):
Default jumper
position [PLC]–[CM1]
and wiring example
return
return
RV
FW
RV
FW
Opt.
Code
Symbol
Function Name
State
Description
—
FW
Forward Run/Stop
ON
Inverter is in Run Mode, motor runs
forward
OFF
Inverter is in Stop Mode, motor stops
01
RV
Reverse Run/Stop
ON
Inverter is in Run Mode, motor runs
reverse
OFF
Inverter is in Stop Mode, motor stops
Valid for
inputs:
C001, C002, C003, C004,
C005, C006, C007, C008
Required
settings:
A002 = 01
Notes:
•
When the Forward Run and Reverse Run
commands are active at the same time, the
inverter enters the Stop Mode.
•
When a terminal associated with either [FW]
or [RV] function is configured for
normally
closed
, the motor starts rotation when that
terminal is disconnected or otherwise has no
input voltage.
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
Example: (Default input configuration
shown—see page
. Jumper position
shown is for –xFU/-xFR models; for –xFE
models, see examples above.)
RV
FW
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......