“C” Group: Intelligent Terminal Functions
Configur
ing Dr
iv
e
P
a
ra
meters
3–54
Output Summary Table
- This table shows all twenty-two functions for the logic output
terminals [11] – [15] at a glance. Detailed function descriptions, related parameters, settings,
and example wiring diagrams are in
“Using Intelligent Output Terminals” on page 4–42
.
“C” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(EU)
–FU
(US)
–FR
(JP)
C031
Terminal [11] active
state
Select logic convention,
two option codes:
00 normally open N.O.
01 normally closed N.C.
✘ ✔
00
00
00
—
>C031 OUT-TM
O/C-11 NO
C032
Terminal [12] active
state
✘ ✔
00
00
00
—
>C032 OUT-TM
O/C-12 NO
C033
Terminal [13] active
state
✘ ✔
00
00
00
—
>C033 OUT-TM
O/C-13 NO
C034
Terminal [14] active
state
✘ ✔
00
00
00
—
>C034 OUT-TM
O/C-14 NO
C035
Terminal [15] active
state
✘ ✔
00
00
00
—
>C035 OUT-TM
O/C-15 NO
C036
Alarm relay terminal
active state
✘ ✔
01
01
01
—
>C036 OUT-TM
O/C-AL NC
Output Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
00
RUN
Run signal
ON
Inverter is in Run Mode, motor running
OFF
Inverter is in Stop Mode, motor stopped
01
FA1
Frequency arrival type
1 – constant speed
ON
when output to motor is at the standard set frequency
F001
OFF
when output to motor is not at the set frequency F001
02
FA2
Frequency arrival type
2 – over-frequency
ON
when output to motor is at or above the FA
Threshold 1 (C042) during accel
OFF
when the output to motor is below the FA Threshold 1
(C043) during decel
03
OL
Overload advance
notice signal (1)
ON
when output current is more than the set Threshold 1
for the overload signal (set with C041)
OFF
when output current is less than the set
Threshold 1for the overload signal
04
OD
Output deviation for
PID control
ON
when PID error is more than the set threshold for the
deviation signal
OFF
when PID error is less than the set threshold for the
deviation signal
05
AL
Alarm signal
ON
when the alarm condition has been met and not reset
OFF
when the alarm had not tripped since the previous
power cycle or since the previous keypad reset
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......