“B” Group: Fine-Tuning Functions
Configur
ing Dr
iv
e
P
a
ra
meters
3–36
Software Lock
Mode
The software lock function keeps personnel from accidentally changing parameters in the
inverter memory. Use B031 to select from various protection levels.
The table below lists all combinations of B031 option codes and the
ON/OFF state of the [SFT] input. Each Check
✔
or Ex
✘
indicates
whether the corresponding parameter(s) can be edited. The Standard
Parameters column below lists Low and High level access for some
lock modes. These refer to the parameter tables throughout this
chapter, each of which includes a column titled
Run Mode Edit
as
shown to the right. The two marks (Check
✔
or Ex
✘
) under the “Lo
Hi” subtitle indicate whether Low-level and/or High-level access
applies to each parameter as defined in the table below. In some lock modes, you can edit only
F001 and the Multi-speed parameter group that includes A020, A220, A320, A021–A035, and
A038 (Jog). However, it does not include A019, Multi-speed operation selection. The editing
access to B031 itself is unique, and is specified in the right-most two columns below.
NOTE:
Since the software lock function B031 is always accessible when the motor is stopped,
this feature is not the same as password protection used in other industrial control devices.
NOTE:
To disable parameter editing when using B031 lock modes 00 and 01, assign the [SFT]
function to one of the intelligent input terminals. See
B031
Lock
Mode
[SFT]
Intelligent
Input
Standard Parameters
F001 and
Multi-speed
B031
Stop
Run
Stop or Run
Stop
Run
00
OFF
✔
Low-level
✔
✔
✘
ON
✘
✘
✘
✔
✘
01
OFF
✔
Low-level
✔
✔
✘
ON
✘
✘
✔
✔
✘
02
(ignored)
✘
✘
✘
✔
✘
03
(ignored)
✘
✘
✔
✔
✘
10
(ignored)
✔
High-level
✔
✔
✔
Run
Mode
Edit
Lo Hi
✘ ✔
“B” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(EU)
–FU
(US)
–FR
(JP)
B031
Software lock mode
selection
Prevents parameter changes
in five options:
00 Low-level access, [SFT]
input blocks all edits
01 Low-level access, [SFT]
input blocks edits
(except F001 and Multi-
speed parameters)
02 No access to edits
03 No access to edits except
F001 and Multi-speed
parameters
10 High-level access,
including B031
✘ ✔
01
01
01
—
>b031 S-LOCK
Mode MD1
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......