SJ300 Inverter
Oper
ati
ons
and Monitor
ing
4–29
Three-wire
Interface
Operation
The 3-wire interface is an industry standard motor control interface. This function uses two
inputs for momentary contact start/stop control, and a third for selecting forward or reverse
direction. To implement the 3-wire interface, assign 20 [STA] (Start), 21 [STP] (Stop), and 22
[F/R] (Forward/Reverse) to three of the intelligent input terminals. Use momentary contact for
Start and Stop. Use a selector switch, such as SPST for the Forward/Reverse input. Be sure to
set the operation command selection A002=01 for input terminal control of motor.
If you have a motor control interface that needs logic-level control (rather than momentary
pulse control), use the [FW] and [RV] inputs instead.
The diagram below shows the use of 3-wire control. STA (Start Motor) is an edge-sensitive
input; an OFF-to-ON transition gives the Start command. The control of direction is level-
sensitive, and the direction may be changed at any time. STP (Stop Motor) is also a level-
sensitive input.
Opt.
Code
Symbol
Function Name
Input
State
Description
20
STA
Start Motor
ON
Start motor rotation on momentary
contact (uses acceleration profile)
OFF
No change to motor operation
21
STP
Stop Motor
ON
No change to motor operation
OFF
Stop motor rotation on momentary contact
(uses deceleration profile)
22
F/R
Forward/Reverse
ON
Select
reverse
direction of rotation
OFF
Select
forward
direction of rotation
Valid for
inputs:
C001, C002, C003, C004,
C005, C006, C007, C008
Required
settings:
A002=01
Notes:
•
The STP logic is inverted. Normally the
switch will be closed, so you open the switch
to stop. In this way, a broken wire causes the
motor to stop automatically (safe design).
•
When you configure the inverter for 3-wire
interface control, the dedicated [FW] terminal
is automatically disabled. The [RV] intelligent
terminal assignment is also disabled.
5
3
1
7
6
4
2
8
FW
TH
PLC
CM1
P24
CM1
See I/O specs on page
.
Example: (Requires input configuration—
see page
. Jumper position shown is
for –xFU/-xFR models; for –xFE models,
see page
.)
F/R
STA
STP
[STA] terminal
[F/R] terminal
[STP] terminal
Motor revolution speed
Forward
Reverse
t
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......