Optional Controlled Decel and Alarm at Power Loss
Oper
ations
a
nd Moni
tor
ing
4–6
The timing diagram below shows a power loss scenario and the related parameter settings.
During the controlled deceleration the inverter itself acts as a load to decelerate the motor. With
either a high-inertia load or a short deceleration time (or both), it is possible that the inverter
impedance will not be low enough to continue linear deceleration and avoid an over-voltage
condition on the DC bus. Use parameter B052 to specify a threshold for the over-voltage. In
this case, the inverter pauses deceleration (runs at constant speed). When the DC bus decays
again below the threshold, linear deceleration resumes. The pause/resume process will repeat as
necessary until the DC bus energy is depleted (under-voltage condition occurs).
NOTE:
(1) Be sure to set the
over-voltage threshold
greater than the
DC bus voltage trigger
level
(B052 > B051) for proper operation.
(2) Once the power loss deceleration function starts, it will complete and stop the motor even if
input power is restored. In that case, it automatically enables the Run mode again.
DC bus (V)
Output
Frequency
Under-voltage
level
B052
B051
B054
B053
t
t
0
0
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......