To calibrate the meter reading, generate a full-scale output (always ON) at terminal [FM]. Then
use parameter B081(gain setting from 0 to 255) to adjust the corresponding full-scale reading
of the meter. For example, when the inverter output frequency is 60 Hz, change the value of
B081 so that the meter reads 60 Hz.
TIP:
When using the analog meter for monitoring, adjust the meter so it has a zero reading
when the [FM] output is zero. Then use scale factor B081 to adjust the [FM] output so the
maximum frequency in the inverter corresponds to a full-scale reading on the meter.
NOTE:
The indicator accuracy after adjustment is about
±
5%. Depending on the motor, the
accuracy may exceed this value.
PWM Smoothing Circuit
– Note that
standard analog output signals are avail-
able on terminals [AM] and [AMI],
covered in the next section. However, you
may also wish to smooth the PWM signal
at the [FM] terminal and convert it to an
analog signal. The [FM] terminal will then
generate a relatively stable DC analog
voltage that represents the output value.
To do this, use the circuit shown to the
right. Note the output impedance of the
circuit is at least 82k
Ω
, so the monitoring
device needs an input impedance of 1M
Ω
or greater. Otherwise, the impedance of
the smoothing circuit will cause a non-
linearity in the reading.
FM Signal Type
The
frequency-modulated
output at terminal [FM] varies its frequency with the inverter output
frequency (when C027=03). The signal at [FM] uses the parameter A004
Maximum frequency
setting
. For example, if A004 = 60 Hz, then the maximum signal value at [FM] will be at
60 Hz. This frequency is digitally controlled for accuracy, and does not use the B081 gain
setting when C027=03 (frequency modulation).
H O2
FM
AM
O
OI
L
FW
TH
PLC
P24
CM1
AMI
+
–
+
–
+
33k
Ω
82k
Ω
Volts
1
μ
F
T
1
[FM] Output Frequency
---------------------------------------------------------
=
Selects FM type output
[FM]
T
[FM] Output Frequency
1
T
---
=
C027=03
t
10V
0V
50% fixed duty cycle
Содержание SJ300 Series
Страница 2: ......
Страница 138: ......
Страница 212: ......
Страница 213: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 243: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 268: ......
Страница 269: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 285: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 294: ......